PortDock

OMRON E5CN Modbus register map

E5□N basic type (E5CN, E5AN, E5EN, E5GN) communication models. Two-byte mode addresses (2000h-): PV, status, SP, alarm values, PID, input type; operation commands via FC06 to 0000h · Temperature controller · E5CN, E5AN, E5EN, E5GN

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)9600 bps — options: 1200, 2400, 4800, 9600, 19200, 38400, 57600
Data · parity · stop8 · Even · 2
Slave ID (factory)1 (1~99)
Max per request106 registers
Manual address styleWire address as is (0-based)

Registers (45)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

45

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
00000 (0x0000)HROperation commandU16W06
FC06 only (address 0000 or FFFF). Write value = command code (high byte) + related information (low byte). Manual example: 01 06 00 00 01 01 49 9A (stop). Accepted regardless of the Communications Writing setting
0 = Communications writing OFF · 1 = Communications writing ON · 256 = Run · 257 = Stop · 512 = Multi-SP set point 0 · 513 = Multi-SP set point 1 · 514 = Multi-SP set point 2 · 515 = Multi-SP set point 3 · 768 = AT cancel · 769 = 100% AT execute · 770 = 40% AT execute · 1024 = Backup mode (also writes EEPROM) · 1025 = RAM write mode · 1280 = Save RAM data · 1536 = Software reset · 1792 = Move to setup area 1 · 2048 = Move to protect level · 2304 = Automatic mode · 2305 = Manual mode · 2816 = Parameter initialization · 3072 = Alarm 1 latch cancel · 3073 = Alarm 2 latch cancel · 3074 = Alarm 3 latch cancel · 3075 = HB alarm latch cancel · 3076 = HS alarm latch cancel · 3077 = OC alarm latch cancel · 3087 = All alarm latch cancel · 3584 = Direct/reverse not inverted · 3585 = Direct/reverse inverted · 4352 = Program reset · 4353 = Program start
5-14~5-16 (PDF 94-96)
20008192 (0x2000)HRPV (process value)S16R03
Integer without decimal point, e.g. 100.0 °C = 03E8h (manual read example)
6-2 (PDF 104)
20018193 (0x2001)HRStatus (lower 16 bits)U16R03
1 = generated/ON
b0 Heater overcurrent (CT1) · b1 Heater current hold (CT1) · b2 A/D converter error · b3 HS alarm (CT1) · b5 Display range exceeded · b6 Input error · b8 Control output (heating) · b9 Control output (cooling) · b10 HB (heater burnout) alarm (CT1) · b11 HB (heater burnout) alarm (CT2) · b12 Alarm 1 · b13 Alarm 2 · b14 Alarm 3 · b15 Program end output
6-2, 6-20 (PDF 104, 122)
20028194 (0x2002)HRInternal set pointS16R03
Integer without decimal point; decimal places follow 2410 (decimal point monitor) / input type
6-2 (PDF 104)
20038195 (0x2003)HRHeater current 1 value monitorU16×0.1 AR03
Range 0 ~ 55 A
6-2 (PDF 104)
20048196 (0x2004)HRMV monitor (heating)S16×0.1 %R03
Standard -5.0 to 105.0, heating/cooling 0.0 to 105.0
6-2 (PDF 104)
20058197 (0x2005)HRMV monitor (cooling)U16×0.1 %R03
Range 0 ~ 105 %
6-2 (PDF 104)
21038451 (0x2103)HRSet pointS16R/W03·06·10
Integer without decimal point; decimal places follow 2410 (decimal point monitor) / input type
6-2 (PDF 104)
21048452 (0x2104)HRAlarm value 1S16R/W03·06·10
-1999 to 9999. Decimal point follows the input setting
6-2~6-3 (PDF 104-105)
21058453 (0x2105)HRAlarm value upper limit 1S16R/W03·06·10
-1999 to 9999. Decimal point follows the input setting
6-2~6-3 (PDF 104-105)
21068454 (0x2106)HRAlarm value lower limit 1S16R/W03·06·10
-1999 to 9999. Decimal point follows the input setting
6-2~6-3 (PDF 104-105)
21078455 (0x2107)HRAlarm value 2S16R/W03·06·10
-1999 to 9999. Decimal point follows the input setting
6-2~6-3 (PDF 104-105)
21088456 (0x2108)HRAlarm value upper limit 2S16R/W03·06·10
-1999 to 9999. Decimal point follows the input setting
6-2~6-3 (PDF 104-105)
21098457 (0x2109)HRAlarm value lower limit 2S16R/W03·06·10
-1999 to 9999. Decimal point follows the input setting
6-2~6-3 (PDF 104-105)
24049220 (0x2404)HRMulti-SP monitorU16R03
Range 0 ~ 3
6-3 (PDF 105)
24079223 (0x2407)HRStatus (upper 16 bits)U16R03
Bits 16-31 of the 32-bit status, read as bits 0-15
b0 Event input 1 · b1 Event input 2 · b2 Event input 3 · b3 Event input 4 · b4 Write mode (1 = RAM write) · b5 EEPROM (1 = RAM ≠ EEPROM) · b6 Setup area (1 = area 1) · b7 AT execution in progress · b8 RUN/STOP (1 = stop) · b9 Communications writing ON · b10 Manual mode · b11 Program start · b12 Heater overcurrent (CT2) · b13 Heater current hold (CT2) · b15 HS alarm (CT2)
6-3, 6-20 (PDF 105, 122)
24109232 (0x2410)HRDecimal point monitorU16R03
Number of decimal places
Range 0 ~ 3
6-3 (PDF 105)
25009472 (0x2500)HROperation/adjustment protectU16R/W03·06·10
0 = No restrictions · 1 = Move to adjustment level prohibited · 2 = Only PV and PV/SP displayed and changeable · 3 = Only PV and PV/SP displayed
6-3 (PDF 105)
25019473 (0x2501)HRInitial setting/communications protectU16R/W03·06·10
0 = Move allowed (advanced function level displayed) · 1 = Move allowed (advanced function level not displayed) · 2 = Move prohibited
6-3 (PDF 105)
25029474 (0x2502)HRSetting change protectU16R/W03·06·10
0 = OFF (changes on display allowed) · 1 = ON (changes on display prohibited)
6-3 (PDF 105)
26009728 (0x2600)HRManual MVS16×0.1 %R/W03·06·10
Standard -5.0 to 105.0, heating/cooling -105.0 to 105.0
6-4 (PDF 106)
27009984 (0x2700)HRCooling coefficientU16×0.01R/W03·06·10
Range 0.01 ~ 99.99
6-4 (PDF 106)
27059989 (0x2705)HRManual reset valueU16×0.1 %R/W03·06·10
Range 0 ~ 100 %
6-4 (PDF 106)
27089992 (0x2708)HRControl period (heating)U16sR/W03·06·10
0 = 0.5 s, 1-99 = 1-99 s. Initial setting level (setup area 1)
6-4 (PDF 106)
27099993 (0x2709)HRControl period (cooling)U16sR/W03·06·10
0 = 0.5 s, 1-99 = 1-99 s. Initial setting level (setup area 1)
6-4 (PDF 106)
271C10012 (0x271C)HRLeakage current 1 monitorU16×0.1 AR03
Range 0 ~ 55 A
6-4 (PDF 106)
272410020 (0x2724)HRHeater current 2 value monitorU16×0.1 AR03
Range 0 ~ 55 A
6-5 (PDF 107)
272610022 (0x2726)HRLeakage current 2 monitorU16×0.1 AR03
Range 0 ~ 55 A
6-5 (PDF 107)
272810024 (0x2728)HRSoak time remainU16R03
Range 0 ~ 9999
6-5 (PDF 107)
271B10011 (0x271B)HRHeater burnout detection 1U16×0.1 AR/W03·06·10
Range 0 ~ 50 A
6-4 (PDF 106)
272510021 (0x2725)HRHeater burnout detection 2U16×0.1 AR/W03·06·10
Range 0 ~ 50 A
6-5 (PDF 107)
290010496 (0x2900)HRMulti-SP SP 0S16R/W03·06·10
Integer without decimal point; decimal places follow 2410 (decimal point monitor) / input type
6-6 (PDF 108)
290E10510 (0x290E)HRMulti-SP SP 1S16R/W03·06·10
Integer without decimal point; decimal places follow 2410 (decimal point monitor) / input type
6-6 (PDF 108)
291C10524 (0x291C)HRMulti-SP SP 2S16R/W03·06·10
Integer without decimal point; decimal places follow 2410 (decimal point monitor) / input type
6-6 (PDF 108)
292A10538 (0x292A)HRMulti-SP SP 3S16R/W03·06·10
Integer without decimal point; decimal places follow 2410 (decimal point monitor) / input type
6-6 (PDF 108)
2A0010752 (0x2A00)HRProportional bandU16×0.1R/W03·06·10
Range 0.1 ~ 999.9
6-6 (PDF 108)
2A0110753 (0x2A01)HRIntegral timeU16sR/W03·06·10
Range 0 ~ 3999 s
6-6 (PDF 108)
2A0210754 (0x2A02)HRDerivative timeU16sR/W03·06·10
0-3999 (1 s) with RT OFF, 0.0-999.9 (0.1 s) with RT ON
6-6 (PDF 108)
2A0510757 (0x2A05)HRMV upper limitS16×0.1 %R/W03·06·10
6-6 (PDF 108)
2A0610758 (0x2A06)HRMV lower limitS16×0.1 %R/W03·06·10
6-6 (PDF 108)
2C0011264 (0x2C00)HRInput type (TC/Pt multi-input models)U16R/W03·06·10
Analog input models: 0 = 4-20 mA, 1 = 0-20 mA, 2 = 1-5 V, 3 = 0-5 V, 4 = 0-10 V. Initial setting level: move to setup area 1 (operation command 0700h) to write. °F ranges in the manual table
0 = Pt -200 to 850 °C · 1 = Pt -199.9 to 500.0 °C · 2 = Pt 0.0 to 100.0 °C · 3 = JPt -199.9 to 500.0 °C · 4 = JPt 0.0 to 100.0 °C · 5 = K -200 to 1300 °C · 6 = K -20.0 to 500.0 °C · 7 = J -100 to 850 °C · 8 = J -20.0 to 400.0 °C · 9 = T -200 to 400 °C · 10 = T -199.9 to 400.0 °C · 11 = E -200 to 600 °C · 12 = L -100 to 850 °C · 13 = U -200 to 400 °C · 14 = U -199.9 to 400.0 °C · 15 = N -200 to 1300 °C · 16 = R 0 to 1700 °C · 17 = S 0 to 1700 °C · 18 = B 100 to 1800 °C · 19 = Infrared sensor K 140 °F/60 °C · 20 = Infrared sensor K 240 °F/120 °C · 21 = Infrared sensor K 280 °F/140 °C · 22 = Infrared sensor K 440 °F/220 °C · 23 = 0 to 50 mV · 24 = W 0 to 2300 °C · 25 = PL II 0 to 1300 °C
6-7 (PDF 109)
2C0111265 (0x2C01)HRTemperature unitU16R/W03·06·10
0 = °C · 1 = °F
6-7 (PDF 109)
2C0911273 (0x2C09)HRScaling lower limitS16R/W03·06·10
-1999 to scaling upper limit - 1 (analog input)
6-7 (PDF 109)
2C0B11275 (0x2C0B)HRScaling upper limitS16R/W03·06·10
Scaling lower limit + 1 to 9999 (analog input)
6-7 (PDF 109)
2C0C11276 (0x2C0C)HRDecimal pointU16R/W03·06·10
0-1 for TC/Pt models, 0-3 for analog input models
6-7 (PDF 109)

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).

Download JSON

Sources