An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 9600 bps — options: 2400, 4800, 9600, 19200, 38400 |
| Data · parity · stop | — · None · 2 |
| Slave ID (factory) | 1 (1~99) |
| Manual address style | Wire address as is (0-based) |
- The manual writes «400001(0000)»: 1-based reference number plus hex communication address in parentheses. Each table starts at (0000), so the parenthesized value is used as the 0-based wire address (pp.19-28).
- Defaults: ADR 01 (01-99), BPS 9600, PRT NON, STP 2 bits, response wait 20 ms (p.28). Data bits are not given in this document. Broadcast is not supported (p.5).
Registers (34)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 000001 (0000) | 0 (0x0000) | CO | Enable AUX output | BIT | R/W | 01·05 | 0 = OFF · 1 = ON (default) p.19 | |
| 000002 (0001) | 1 (0x0001) | CO | Enable compressor output | BIT | R/W | 01·05 | 0 = OFF · 1 = ON (default) p.19 | |
| 100003 (0002) | 2 (0x0002) | DI | COMP output indicator | BIT | R | 02 | p.19 | |
| 100004 (0003) | 3 (0x0003) | DI | DEF (defrost) output indicator | BIT | R | 02 | p.19 | |
| 100005 (0004) | 4 (0x0004) | DI | FAN (evaporator fan) output indicator | BIT | R | 02 | p.19 | |
| 100006 (0005) | 5 (0x0005) | DI | AUX output indicator | BIT | R | 02 | p.19 | |
| 100010 (0009) | 9 (0x0009) | DI | Digital input | BIT | R | 02 | p.19 | |
| 301001 (03E8) | 1000 (0x03E8) | IR | Present value (PV) | S16 | R | 04 | SV low to high limit. 30001 = OPEN, 30000 = HHHH, −30000 = LLLL. Decimals follow 301013 decimal point position (0 or 0.0), so no fixed scale p.21 | |
| 301002 (03E9) | 1001 (0x03E9) | IR | SV setting value | S16 | R | 04 | Decimals follow 301013 decimal point position (0 or 0.0), so no fixed scale p.21 | |
| 301003 (03EA) | 1002 (0x03EA) | IR | DpT display selection | U16 | R | 04 | 0 = S1 · 1 = S2 · 2 = S3 · 3 = VS (virtual temperature) p.21 | |
| 301004 (03EB) | 1003 (0x03EB) | IR | Temperature unit | U16 | R | 04 | 0 = °C · 1 = °F p.21 | |
| 301005 (03EC) | 1004 (0x03EC) | IR | Monitoring time | U16 | h | R | 04 | Range 0 ~ 100 h p.21 |
| 301006 (03ED) | 1005 (0x03ED) | IR | Max. temperature value | S16 | R | 04 | Decimals follow 301013 decimal point position (0 or 0.0), so no fixed scale p.21 | |
| 301007 (03EE) | 1006 (0x03EE) | IR | Min. temperature value | S16 | R | 04 | Decimals follow 301013 decimal point position (0 or 0.0), so no fixed scale p.21 | |
| 301008 (03EF) | 1007 (0x03EF) | IR | Front indicator status | U16 | R | 04 | b0 °C · b1 °F · b2 COMP · b3 DEF · b4 FAN · b5 AUX · b6 ▲ deviation · b7 ■ deviation · b8 ▼ deviation · b9 DI input p.21 | |
| 400001 (0000) | 0 (0x0000) | HR | SV setting | S16 | R/W | 03·06·10 | Default 0. Decimals follow 301013 decimal point position (0 or 0.0), so no fixed scale p.22 | |
| 400002 (0001) | 1 (0x0001) | HR | DpT display selection | U16 | R/W | 03·06·10 | 0 = S1 (default) · 1 = S2 · 2 = S3 · 3 = VS p.22 | |
| 400101 (0064) | 100 (0x0064) | HR | INT input type | U16 | R/W | 03·06·10 | 0 = NsH (default) · 1 = NsL · 2 = N1H · 3 = N1L · 4 = DpH · 5 = DpL p.23 | |
| 400105 (0068) | 104 (0x0068) | HR | UNT temperature unit | U16 | R/W | 03·06·10 | 0 = °C (default) · 1 = °F p.23 | |
| 400151 (0096) | 150 (0x0096) | HR | OFT compressor output mode | U16 | R/W | 03·06·10 | 0 = C (cooling, default) · 1 = H (heating) p.24 | |
| 400154 (0099) | 153 (0x0099) | HR | HSV SV high limit | S16 | R/W | 03·06·10 | Default 99 °C. Decimals follow 301013 decimal point position (0 or 0.0), so no fixed scale p.24 | |
| 400155 (009A) | 154 (0x009A) | HR | LSV SV low limit | S16 | R/W | 03·06·10 | Default -40 °C. Decimals follow 301013 decimal point position (0 or 0.0), so no fixed scale p.24 | |
| 400165 (00A4) | 164 (0x00A4) | HR | SDL compressor start-up delay | U16 | min | R/W | 03·06·10 | Range 0 ~ 60 min p.24 |
| 400167 (00A6) | 166 (0x00A6) | HR | RDL compressor restart delay | U16 | min | R/W | 03·06·10 | Range 0 ~ 60 min p.24 |
| 400168 (00A7) | 167 (0x00A7) | HR | ONT compressor min. operation time | U16 | min | R/W | 03·06·10 | Range 0 ~ 60 min p.24 |
| 400201 (00C8) | 200 (0x00C8) | HR | DEF defrost method | U16 | R/W | 03·06·10 | 0 = hTM (default) · 1 = gTM · 2 = hTT · 3 = gTT p.25 | |
| 400202 (00C9) | 201 (0x00C9) | HR | DIN defrost cycle | U16 | h | R/W | 03·06·10 | 0-24 or 0-100; default 4 p.25 |
| 400251 (00FA) | 250 (0x00FA) | HR | AL alarm operation mode | U16 | R/W | 03·06·10 | 0 = OFF · 1 = AlD (default) p.27 | |
| 400256 (00FF) | 255 (0x00FF) | HR | aON alarm ON delay | U16 | min | R/W | 03·06·10 | Range 0 ~ 60 min p.27 |
| 400305 (0130) | 304 (0x0130) | HR | ADR communication address | U16 | R/W | 03·06·10 | Range 1 ~ 99 p.28 | |
| 400306 (0131) | 305 (0x0131) | HR | BPS communication speed | U16 | R/W | 03·06·10 | 0 = 2400 bps · 1 = 4800 bps · 2 = 9600 bps (default) · 3 = 19200 bps · 4 = 38400 bps p.28 | |
| 400307 (0132) | 306 (0x0132) | HR | PRT parity | U16 | R/W | 03·06·10 | 0 = NON (default) · 1 = EVN · 2 = ODD p.28 | |
| 400308 (0133) | 307 (0x0133) | HR | STP stop bit | U16 | R/W | 03·06·10 | 0 = 1 bit · 1 = 2 bits (default) p.28 | |
| 400310 (0135) | 309 (0x0135) | HR | COW communication write | U16 | R/W | 03·06·10 | 0 = EnA enabled (default) · 1 = DsA disabled p.28 |
Notes
- Temperature values depend on the decimal point (301013). 301009-301013 and 302001- have no hex address in parentheses, and items whose range text is garbled (hysteresis, correction, defrost times) are left out.
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- autonics/tf3.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- User Manual for Communication Temperature Controllers TF3 Series MCT-TF3C1-V1.3-EN — Autonics, MCT-TF3C1-V1.3-EN · p.5 protocol, pp.19-28 Modbus mapping table (printed page = PDF page) · checked 2026-10-31