Autonics TF3 Series Modbus register map

Modbus RTU (no broadcast). Coils (AUX and compressor outputs), discrete inputs (output indicators, DI), input registers (PV, SV, max/min), holding registers (settings, FC 03/06/16). · Temperature controller

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)9600 bps — options: 2400, 4800, 9600, 19200, 38400
Data · parity · stop— · None · 2
Slave ID (factory)1 (1~99)
Manual address styleWire address as is (0-based)

Registers (34)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

34

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
000001 (0000)0 (0x0000)COEnable AUX outputBITR/W01·05
0 = OFF · 1 = ON (default)
p.19
000002 (0001)1 (0x0001)COEnable compressor outputBITR/W01·05
0 = OFF · 1 = ON (default)
p.19
100003 (0002)2 (0x0002)DICOMP output indicatorBITR02
p.19
100004 (0003)3 (0x0003)DIDEF (defrost) output indicatorBITR02
p.19
100005 (0004)4 (0x0004)DIFAN (evaporator fan) output indicatorBITR02
p.19
100006 (0005)5 (0x0005)DIAUX output indicatorBITR02
p.19
100010 (0009)9 (0x0009)DIDigital inputBITR02
p.19
301001 (03E8)1000 (0x03E8)IRPresent value (PV)S16R04
SV low to high limit. 30001 = OPEN, 30000 = HHHH, −30000 = LLLL. Decimals follow 301013 decimal point position (0 or 0.0), so no fixed scale
p.21
301002 (03E9)1001 (0x03E9)IRSV setting valueS16R04
Decimals follow 301013 decimal point position (0 or 0.0), so no fixed scale
p.21
301003 (03EA)1002 (0x03EA)IRDpT display selectionU16R04
0 = S1 · 1 = S2 · 2 = S3 · 3 = VS (virtual temperature)
p.21
301004 (03EB)1003 (0x03EB)IRTemperature unitU16R04
0 = °C · 1 = °F
p.21
301005 (03EC)1004 (0x03EC)IRMonitoring timeU16hR04
Range 0 ~ 100 h
p.21
301006 (03ED)1005 (0x03ED)IRMax. temperature valueS16R04
Decimals follow 301013 decimal point position (0 or 0.0), so no fixed scale
p.21
301007 (03EE)1006 (0x03EE)IRMin. temperature valueS16R04
Decimals follow 301013 decimal point position (0 or 0.0), so no fixed scale
p.21
301008 (03EF)1007 (0x03EF)IRFront indicator statusU16R04
b0 °C · b1 °F · b2 COMP · b3 DEF · b4 FAN · b5 AUX · b6 ▲ deviation · b7 ■ deviation · b8 ▼ deviation · b9 DI input
p.21
400001 (0000)0 (0x0000)HRSV settingS16R/W03·06·10
Default 0. Decimals follow 301013 decimal point position (0 or 0.0), so no fixed scale
p.22
400002 (0001)1 (0x0001)HRDpT display selectionU16R/W03·06·10
0 = S1 (default) · 1 = S2 · 2 = S3 · 3 = VS
p.22
400101 (0064)100 (0x0064)HRINT input typeU16R/W03·06·10
0 = NsH (default) · 1 = NsL · 2 = N1H · 3 = N1L · 4 = DpH · 5 = DpL
p.23
400105 (0068)104 (0x0068)HRUNT temperature unitU16R/W03·06·10
0 = °C (default) · 1 = °F
p.23
400151 (0096)150 (0x0096)HROFT compressor output modeU16R/W03·06·10
0 = C (cooling, default) · 1 = H (heating)
p.24
400154 (0099)153 (0x0099)HRHSV SV high limitS16R/W03·06·10
Default 99 °C. Decimals follow 301013 decimal point position (0 or 0.0), so no fixed scale
p.24
400155 (009A)154 (0x009A)HRLSV SV low limitS16R/W03·06·10
Default -40 °C. Decimals follow 301013 decimal point position (0 or 0.0), so no fixed scale
p.24
400165 (00A4)164 (0x00A4)HRSDL compressor start-up delayU16minR/W03·06·10
Range 0 ~ 60 min
p.24
400167 (00A6)166 (0x00A6)HRRDL compressor restart delayU16minR/W03·06·10
Range 0 ~ 60 min
p.24
400168 (00A7)167 (0x00A7)HRONT compressor min. operation timeU16minR/W03·06·10
Range 0 ~ 60 min
p.24
400201 (00C8)200 (0x00C8)HRDEF defrost methodU16R/W03·06·10
0 = hTM (default) · 1 = gTM · 2 = hTT · 3 = gTT
p.25
400202 (00C9)201 (0x00C9)HRDIN defrost cycleU16hR/W03·06·10
0-24 or 0-100; default 4
p.25
400251 (00FA)250 (0x00FA)HRAL alarm operation modeU16R/W03·06·10
0 = OFF · 1 = AlD (default)
p.27
400256 (00FF)255 (0x00FF)HRaON alarm ON delayU16minR/W03·06·10
Range 0 ~ 60 min
p.27
400305 (0130)304 (0x0130)HRADR communication addressU16R/W03·06·10
Range 1 ~ 99
p.28
400306 (0131)305 (0x0131)HRBPS communication speedU16R/W03·06·10
0 = 2400 bps · 1 = 4800 bps · 2 = 9600 bps (default) · 3 = 19200 bps · 4 = 38400 bps
p.28
400307 (0132)306 (0x0132)HRPRT parityU16R/W03·06·10
0 = NON (default) · 1 = EVN · 2 = ODD
p.28
400308 (0133)307 (0x0133)HRSTP stop bitU16R/W03·06·10
0 = 1 bit · 1 = 2 bits (default)
p.28
400310 (0135)309 (0x0135)HRCOW communication writeU16R/W03·06·10
0 = EnA enabled (default) · 1 = DsA disabled
p.28

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).

Download JSON

Sources