Hanyoung Nux NX Series Modbus register map

RS485/RS422. Modbus RTU/ASCII access to D-registers: FC 03 read, FC 06/16 write. The factory protocol is PC-LINK, so P-rS must be changed for Modbus. · Temperature controller · NX1, NX2, NX3, NX4, NX7, NX9

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU, Modbus ASCII
Baud (factory)9600 bps — options: 2400, 4800, 9600, 14400, 19200
Data · parity · stop8 · Even · 1
Slave ID (factory)1 (1~99)
Max per request32 registers
Manual address styleWire address as is (0-based)

Registers (44)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

44

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
D00011 (0x0001)HRNPV present value (PV)S16R03
Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale
printed p.41 (PDF p.42)
D00022 (0x0002)HRNSV current set value (SV)S16R03
Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale
printed p.41 (PDF p.42)
D00044 (0x0004)HRS SV current setting valueS16R03
Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale
printed p.41 (PDF p.42)
D00055 (0x0005)HRMVOUT control output valueS16×0.1 %R03
OUT1 for standard type; total for heating/cooling type
printed p.41 (PDF p.42)
D00066 (0x0006)HRCH1OUT OUT1 control output valueS16×0.1 %R03
printed p.41 (PDF p.42)
D00077 (0x0007)HRCH2OUT OUT2 control output value (heating/cooling)S16×0.1 %R03
printed p.41 (PDF p.42)
D00088 (0x0008)HRPIDNO SV and PID group in useU16R03
With ZONE off: SV and PID group 1-3; with ZONE on: PID group 1-3
Range 1 ~ 3
printed p.41 (PDF p.42)
D00099 (0x0009)HRALMSTS alarm 1 and 2 statusU16R03
0 = Alarm 1 off, alarm 2 off · 1 = Alarm 1 on, alarm 2 off · 2 = Alarm 1 off, alarm 2 on · 3 = Alarm 1 on, alarm 2 on
printed p.41 (PDF p.42)
D001414 (0x000E)HRH1CM heater break current measured valueU16R03
printed p.41 (PDF p.42)
D001616 (0x0010)HRADESTS AD error statusU16R03
1 = AD conversion error
printed p.41 (PDF p.42)
D001717 (0x0011)HRERRSTS input error statusU16R03
b0 Sensor burn-out · b1 RJC error · b2 Input out of range · b3 Less than input range
printed p.41 (PDF p.42)
D001818 (0x0012)HRAT_STS auto-tuning statusU16R03
0 = AT end · 9999 = AT in progress
printed p.41 (PDF p.42)
D0102102 (0x0066)HRZONE zone functionU16R/W03·06·10
0 = Off · 1 = On
printed p.41 (PDF p.42)
D0103103 (0x0067)HRFUZZY fuzzy functionU16R/W03·06·10
0 = Off · 1 = On
printed p.41 (PDF p.42)
D0106106 (0x006A)HRDI.SL external contact input (DI) functionU16R/W03·06·10
0 = Off · 1 = On
printed p.41 (PDF p.42)
D0121121 (0x0079)HRMANMV manual output valueU16%R/W03·06·10
Range 0 ~ 100 %
printed p.41 (PDF p.42)
D0300300 (0x012C)HRSVNO set value numberU16R/W03·06·10
Range 1 ~ 3
printed p.41 (PDF p.42)
D0301301 (0x012D)HRSV1 set value 1S16R/W03·06·10
Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale
printed p.41 (PDF p.42)
D0302302 (0x012E)HRSV2 set value 2S16R/W03·06·10
Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale
printed p.41 (PDF p.42)
D0303303 (0x012F)HRSV3 set value 3S16R/W03·06·10
Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale
printed p.41 (PDF p.42)
D0305305 (0x0131)HRAT MODE auto-tuning modeU16R/W03·06·10
0 = Standard automatic calculation · 1 = Low PV type automatic calculation
printed p.41 (PDF p.42)
D0306306 (0x0132)HRAT auto-tuningU16R/W03·06·10
0 off, 1-4
Range 0 ~ 4
printed p.41 (PDF p.42)
D0310310 (0x0136)HR1.P PID group 1 proportional bandU16×0.1 %R/W03·06·10
Range 0 ~ 999.9 %
printed p.41 (PDF p.42)
D0311311 (0x0137)HR1.I PID group 1 integral timeU16sR/W03·06·10
Range 0 ~ 6000 s
printed p.41 (PDF p.42)
D0312312 (0x0138)HR1.D PID group 1 derivative timeU16sR/W03·06·10
Range 0 ~ 6000 s
printed p.41 (PDF p.42)
D0313313 (0x0139)HR1.MR PID group 1 manual resetS16×0.1 %R/W03·06·10
Range -5 ~ 105 %
printed p.41 (PDF p.42)
D0400400 (0x0190)HRHBA heater break alarm currentU16AR/W03·06·10
0 off, 1-50 A
Range 0 ~ 50 A
printed p.41 (PDF p.42)
D0410410 (0x019A)HRA1TY alarm 1 typeU16R/W03·06·10
0 off, 1-21
Range 0 ~ 21
printed p.41 (PDF p.42)
D0411411 (0x019B)HRA2TY alarm 2 typeU16R/W03·06·10
0 off, 1-21
Range 0 ~ 21
printed p.41 (PDF p.42)
D0416416 (0x01A0)HRAL-1 alarm 1 set valueS16R/W03·06·10
Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale
printed p.41 (PDF p.42)
D0417417 (0x01A1)HRAL-2 alarm 2 set valueS16R/W03·06·10
Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale
printed p.41 (PDF p.42)
D0600600 (0x0258)HROUT output typeU16R/W03·06·10
Range 0 ~ 12
printed p.41 (PDF p.42)
D0601601 (0x0259)HRo.ACT output actionU16R/W03·06·10
0 = Reverse action (heating) · 1 = Forward action (cooling)
printed p.41 (PDF p.42)
D0602602 (0x025A)HRCT cycle timeU16sR/W03·06·10
Range 1 ~ 1000 s
printed p.41 (PDF p.42)
D0607607 (0x025F)HROL-H output upper limitS16×0.1 %R/W03·06·10
printed p.41 (PDF p.42)
D0608608 (0x0260)HROL-L output lower limitS16×0.1 %R/W03·06·10
printed p.41 (PDF p.42)
D0610610 (0x0262)HRINP input typeU16R/W03·06·10
Range 1 ~ 31
printed p.41 (PDF p.42)
D0611611 (0x0263)HRUNIT temperature unitU16R/W03·06·10
0 = °C · 1 = °F
printed p.41 (PDF p.42)
D0612612 (0x0264)HRFR-H range upper limitS16R/W03·06·10
Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale
printed p.41 (PDF p.42)
D0613613 (0x0265)HRFR-L range lower limitS16R/W03·06·10
Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale
printed p.41 (PDF p.42)
D0614614 (0x0266)HRDP-P decimal point position (voltage input)U16R/W03·06·10
0 = No decimal point · 1 = 1 decimal place · 2 = 2 decimal places · 3 = 3 decimal places
printed p.41 (PDF p.42)
D0617617 (0x0269)HRFILT measured value filterU16sR/W03·06·10
0 off
Range 0 ~ 120 s
printed p.41 (PDF p.42)
D0618618 (0x026A)HRBIAS measured value biasS16R/W03·06·10
Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale
printed p.41 (PDF p.42)
D0619619 (0x026B)HRB.OUT action on input breakU16R/W03·06·10
0 = Off · 1 = UP · 2 = DOWN
printed p.41 (PDF p.42)

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).