An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU, Modbus ASCII |
|---|---|
| Baud (factory) | 9600 bps — options: 2400, 4800, 9600, 14400, 19200 |
| Data · parity · stop | 8 · Even · 1 |
| Slave ID (factory) | 1 (1~99) |
| Max per request | 32 registers |
| Manual address style | Wire address as is (0-based) |
- Wire address = D-register number (decimal) written in hex as is. Evidence: the protocol document's Modbus examples (PDF pp.27-31) send SV1 (D0301) as 012D: 11 03 01 2D 00 03 96 AE, CRC recomputed and correct. The same document's p.26 text (subtract 40001 to get 012C) contradicts the examples and is not followed.
- Factory defaults (printed p.31, PDF p.32): protocol P-rS = 0 (PC-LINK); Modbus RTU = 3, ASCII = 2. Speed bPS = 4 (9600), parity 1 (EVEN), 1 stop bit, 8 data bits, address 1, response time 0. Addresses 1-99, up to 31 units.
- The NX1 DC model supports only PC-LINK / PC-LINK SUM, not Modbus (printed p.31). FC 03 reads up to 32 registers, FC 16 writes up to 16; FC 08 diagnostics; address 0 is broadcast with no reply (protocol document PDF pp.20-25).
Registers (44)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| D0001 | 1 (0x0001) | HR | NPV present value (PV) | S16 | R | 03 | Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale printed p.41 (PDF p.42) | |
| D0002 | 2 (0x0002) | HR | NSV current set value (SV) | S16 | R | 03 | Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale printed p.41 (PDF p.42) | |
| D0004 | 4 (0x0004) | HR | S SV current setting value | S16 | R | 03 | Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale printed p.41 (PDF p.42) | |
| D0005 | 5 (0x0005) | HR | MVOUT control output value | S16 | ×0.1 % | R | 03 | OUT1 for standard type; total for heating/cooling type printed p.41 (PDF p.42) |
| D0006 | 6 (0x0006) | HR | CH1OUT OUT1 control output value | S16 | ×0.1 % | R | 03 | printed p.41 (PDF p.42) |
| D0007 | 7 (0x0007) | HR | CH2OUT OUT2 control output value (heating/cooling) | S16 | ×0.1 % | R | 03 | printed p.41 (PDF p.42) |
| D0008 | 8 (0x0008) | HR | PIDNO SV and PID group in use | U16 | R | 03 | With ZONE off: SV and PID group 1-3; with ZONE on: PID group 1-3 Range 1 ~ 3 printed p.41 (PDF p.42) | |
| D0009 | 9 (0x0009) | HR | ALMSTS alarm 1 and 2 status | U16 | R | 03 | 0 = Alarm 1 off, alarm 2 off · 1 = Alarm 1 on, alarm 2 off · 2 = Alarm 1 off, alarm 2 on · 3 = Alarm 1 on, alarm 2 on printed p.41 (PDF p.42) | |
| D0014 | 14 (0x000E) | HR | H1CM heater break current measured value | U16 | R | 03 | printed p.41 (PDF p.42) | |
| D0016 | 16 (0x0010) | HR | ADESTS AD error status | U16 | R | 03 | 1 = AD conversion error printed p.41 (PDF p.42) | |
| D0017 | 17 (0x0011) | HR | ERRSTS input error status | U16 | R | 03 | b0 Sensor burn-out · b1 RJC error · b2 Input out of range · b3 Less than input range printed p.41 (PDF p.42) | |
| D0018 | 18 (0x0012) | HR | AT_STS auto-tuning status | U16 | R | 03 | 0 = AT end · 9999 = AT in progress printed p.41 (PDF p.42) | |
| D0102 | 102 (0x0066) | HR | ZONE zone function | U16 | R/W | 03·06·10 | 0 = Off · 1 = On printed p.41 (PDF p.42) | |
| D0103 | 103 (0x0067) | HR | FUZZY fuzzy function | U16 | R/W | 03·06·10 | 0 = Off · 1 = On printed p.41 (PDF p.42) | |
| D0106 | 106 (0x006A) | HR | DI.SL external contact input (DI) function | U16 | R/W | 03·06·10 | 0 = Off · 1 = On printed p.41 (PDF p.42) | |
| D0121 | 121 (0x0079) | HR | MANMV manual output value | U16 | % | R/W | 03·06·10 | Range 0 ~ 100 % printed p.41 (PDF p.42) |
| D0300 | 300 (0x012C) | HR | SVNO set value number | U16 | R/W | 03·06·10 | Range 1 ~ 3 printed p.41 (PDF p.42) | |
| D0301 | 301 (0x012D) | HR | SV1 set value 1 | S16 | R/W | 03·06·10 | Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale printed p.41 (PDF p.42) | |
| D0302 | 302 (0x012E) | HR | SV2 set value 2 | S16 | R/W | 03·06·10 | Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale printed p.41 (PDF p.42) | |
| D0303 | 303 (0x012F) | HR | SV3 set value 3 | S16 | R/W | 03·06·10 | Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale printed p.41 (PDF p.42) | |
| D0305 | 305 (0x0131) | HR | AT MODE auto-tuning mode | U16 | R/W | 03·06·10 | 0 = Standard automatic calculation · 1 = Low PV type automatic calculation printed p.41 (PDF p.42) | |
| D0306 | 306 (0x0132) | HR | AT auto-tuning | U16 | R/W | 03·06·10 | 0 off, 1-4 Range 0 ~ 4 printed p.41 (PDF p.42) | |
| D0310 | 310 (0x0136) | HR | 1.P PID group 1 proportional band | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 999.9 % printed p.41 (PDF p.42) |
| D0311 | 311 (0x0137) | HR | 1.I PID group 1 integral time | U16 | s | R/W | 03·06·10 | Range 0 ~ 6000 s printed p.41 (PDF p.42) |
| D0312 | 312 (0x0138) | HR | 1.D PID group 1 derivative time | U16 | s | R/W | 03·06·10 | Range 0 ~ 6000 s printed p.41 (PDF p.42) |
| D0313 | 313 (0x0139) | HR | 1.MR PID group 1 manual reset | S16 | ×0.1 % | R/W | 03·06·10 | Range -5 ~ 105 % printed p.41 (PDF p.42) |
| D0400 | 400 (0x0190) | HR | HBA heater break alarm current | U16 | A | R/W | 03·06·10 | 0 off, 1-50 A Range 0 ~ 50 A printed p.41 (PDF p.42) |
| D0410 | 410 (0x019A) | HR | A1TY alarm 1 type | U16 | R/W | 03·06·10 | 0 off, 1-21 Range 0 ~ 21 printed p.41 (PDF p.42) | |
| D0411 | 411 (0x019B) | HR | A2TY alarm 2 type | U16 | R/W | 03·06·10 | 0 off, 1-21 Range 0 ~ 21 printed p.41 (PDF p.42) | |
| D0416 | 416 (0x01A0) | HR | AL-1 alarm 1 set value | S16 | R/W | 03·06·10 | Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale printed p.41 (PDF p.42) | |
| D0417 | 417 (0x01A1) | HR | AL-2 alarm 2 set value | S16 | R/W | 03·06·10 | Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale printed p.41 (PDF p.42) | |
| D0600 | 600 (0x0258) | HR | OUT output type | U16 | R/W | 03·06·10 | Range 0 ~ 12 printed p.41 (PDF p.42) | |
| D0601 | 601 (0x0259) | HR | o.ACT output action | U16 | R/W | 03·06·10 | 0 = Reverse action (heating) · 1 = Forward action (cooling) printed p.41 (PDF p.42) | |
| D0602 | 602 (0x025A) | HR | CT cycle time | U16 | s | R/W | 03·06·10 | Range 1 ~ 1000 s printed p.41 (PDF p.42) |
| D0607 | 607 (0x025F) | HR | OL-H output upper limit | S16 | ×0.1 % | R/W | 03·06·10 | printed p.41 (PDF p.42) |
| D0608 | 608 (0x0260) | HR | OL-L output lower limit | S16 | ×0.1 % | R/W | 03·06·10 | printed p.41 (PDF p.42) |
| D0610 | 610 (0x0262) | HR | INP input type | U16 | R/W | 03·06·10 | Range 1 ~ 31 printed p.41 (PDF p.42) | |
| D0611 | 611 (0x0263) | HR | UNIT temperature unit | U16 | R/W | 03·06·10 | 0 = °C · 1 = °F printed p.41 (PDF p.42) | |
| D0612 | 612 (0x0264) | HR | FR-H range upper limit | S16 | R/W | 03·06·10 | Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale printed p.41 (PDF p.42) | |
| D0613 | 613 (0x0265) | HR | FR-L range lower limit | S16 | R/W | 03·06·10 | Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale printed p.41 (PDF p.42) | |
| D0614 | 614 (0x0266) | HR | DP-P decimal point position (voltage input) | U16 | R/W | 03·06·10 | 0 = No decimal point · 1 = 1 decimal place · 2 = 2 decimal places · 3 = 3 decimal places printed p.41 (PDF p.42) | |
| D0617 | 617 (0x0269) | HR | FILT measured value filter | U16 | s | R/W | 03·06·10 | 0 off Range 0 ~ 120 s printed p.41 (PDF p.42) |
| D0618 | 618 (0x026A) | HR | BIAS measured value bias | S16 | R/W | 03·06·10 | Decimals follow the input type and range (table note *1: 100.0 °C is sent as 1000, 100 without decimals), so no fixed scale printed p.41 (PDF p.42) | |
| D0619 | 619 (0x026B) | HR | B.OUT action on input break | U16 | R/W | 03·06·10 | 0 = Off · 1 = UP · 2 = DOWN printed p.41 (PDF p.42) |
Notes
- Values marked *2 (outputs, proportional band, manual reset, output limits) have one decimal (scale 0.1). Temperature-type values marked *1 depend on input type and decimal setting, so they have no fixed scale. EU(0-100 %) ranges are relative to the input range.
- Left out: 0013 OUT2_IND (value meanings not given), 0104 ARW and 0604 HYS (two different units/decimals in one cell), PID groups 2-3, ramp 0108-0110, retransmission 0500-0502 and others. The manual PDF's fonts do not extract as text, so values were read from the rendered pages.
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- hanyoung-nux/nx.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/