OMRON E5CC Modbus register map

E5□C (E5CC, E5EC, E5AC, E5DC, E5GC) communication models. Two-byte mode addresses (2000h-): PV, status, SP, alarm values, PID, input type; operation commands via FC06 to 0000h · Temperature controller · E5CC, E5EC, E5AC, E5DC, E5GC

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)9600 bps — options: 9600, 19200, 38400, 57600
Data · parity · stop8 · Even · 1
Slave ID (factory)1 (1~99)
Max per request106 registers
Manual address styleWire address as is (0-based)

Registers (26)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

26

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
00000 (0x0000)HROperation commandU16W06
FC06 only. Value = command code (high byte) + related information (low byte), e.g. STOP = 0101h. Manual example: 01 06 00 00 01 01 49 9A. Multi-SP (02xx), alarm latch cancel (0Cxx) etc. in the table on pp.2-16 to 2-17
0 = Communications writing OFF · 1 = Communications writing ON · 256 = Run · 257 = Stop · 768 = AT cancel · 769 = 100% AT execute · 770 = 40% AT execute · 1024 = Backup mode · 1025 = RAM write mode · 1280 = Save RAM data · 1536 = Software reset · 1792 = Move to setup area 1 · 2048 = Move to protect level · 2304 = Automatic mode · 2305 = Manual mode · 2816 = Parameter initialization
4-12, 4-14 (PDF 90, 92)
20008192 (0x2000)HRPV (process value)S16R03
Integer without decimal point, e.g. 100.0 °C = 03E8h (manual read example)
5-2 (PDF 96)
20018193 (0x2001)HRStatus (lower 16 bits)U16R03
1 = generated/ON
b0 Heater overcurrent (CT1) · b1 Heater current hold (CT1) · b2 A/D converter error · b3 HS alarm (CT1) · b4 RSP input error · b6 Input error · b7 Potentiometer input error · b8 Control output (heating)/open output · b9 Control output (cooling)/close output · b10 HB alarm (CT1) · b11 HB alarm (CT2) · b12 Alarm 1 · b13 Alarm 2 · b14 Alarm 3 · b15 Program end output
5-2, 3-25 (PDF 96, 77)
20028194 (0x2002)HRInternal set pointS16R03
Integer without decimal point; decimal places follow 2410h (decimal point monitor) / input type
5-2 (PDF 96)
20038195 (0x2003)HRHeater current 1 value monitorU16×0.1 AR03
Range 0 ~ 55 A
5-2 (PDF 96)
20048196 (0x2004)HRMV monitor (heating)S16×0.1 %R03
Range -5 ~ 105 %
5-2 (PDF 96)
20058197 (0x2005)HRMV monitor (cooling)U16×0.1 %R03
Range 0 ~ 105 %
5-2 (PDF 96)
21038451 (0x2103)HRSet pointS16R/W03·06·10
Integer without decimal point; decimal places follow 2410h (decimal point monitor) / input type
5-2 (PDF 96)
21048452 (0x2104)HRAlarm value 1S16R/W03·06·10
Decimal point follows the input setting
Range -1999 ~ 9999
5-2 (PDF 96)
21058453 (0x2105)HRAlarm value upper limit 1S16R/W03·06·10
Decimal point follows the input setting
Range -1999 ~ 9999
5-2 (PDF 96)
21068454 (0x2106)HRAlarm value lower limit 1S16R/W03·06·10
Decimal point follows the input setting
Range -1999 ~ 9999
5-2 (PDF 96)
21078455 (0x2107)HRAlarm value 2S16R/W03·06·10
Decimal point follows the input setting
Range -1999 ~ 9999
5-2 (PDF 96)
21088456 (0x2108)HRAlarm value upper limit 2S16R/W03·06·10
Decimal point follows the input setting
Range -1999 ~ 9999
5-2 (PDF 96)
21098457 (0x2109)HRAlarm value lower limit 2S16R/W03·06·10
Decimal point follows the input setting
Range -1999 ~ 9999
5-2 (PDF 96)
24049220 (0x2404)HRMulti-SP No. monitorU16R03
Range 0 ~ 7
5-2 (PDF 96)
24079223 (0x2407)HRStatus (upper 16 bits)U16R03
Bits 16-31 of the 32-bit status, read as bits 0-15
b0 Event input 1 · b1 Event input 2 · b2 Event input 3 · b3 Event input 4 · b4 Write mode (0 backup / 1 RAM write) · b5 Non-volatile memory (1 = RAM differs) · b6 Setup area (0 = area 0 / 1 = area 1) · b7 AT in progress · b8 RUN/STOP (0 = run / 1 = stop) · b9 Communications writing enabled · b10 Auto/manual (1 = manual) · b11 Program start · b12 Heater overcurrent (CT2) · b13 Heater current hold (CT2) · b15 HS alarm (CT2)
5-2, 3-25 (PDF 96, 77)
24109232 (0x2410)HRDecimal point monitorU16R03
Number of decimal places
Range 0 ~ 3
5-2 (PDF 96)
2A0010752 (0x2A00)HRProportional bandU16×0.1R/W03·06·10
Range 0.1 ~ 999.9
5-6 (PDF 100)
2A0110753 (0x2A01)HRIntegral timeU16sR/W03·06·10
1 s (0-9999) or 0.1 s (0.0-999.9) depending on the integral/derivative time unit setting
5-6 (PDF 100)
2A0210754 (0x2A02)HRDerivative timeU16sR/W03·06·10
Unit as for the integral time
5-6 (PDF 100)
2A0510757 (0x2A05)HRMV upper limitS16×0.1 %R/W03·06·10
5-6 (PDF 100)
2A0610758 (0x2A06)HRMV lower limitS16×0.1 %R/W03·06·10
5-6 (PDF 100)
2C0011264 (0x2C00)HRInput typeU16R/W03·06·10
Initial setting level: move to setup area 1 (operation command 0700h) to write. °F ranges in the manual table
0 = Pt100 -200 to 850 °C · 1 = Pt100 -199.9 to 500.0 °C · 2 = Pt100 0.0 to 100.0 °C · 3 = JPt100 -199.9 to 500.0 °C · 4 = JPt100 0.0 to 100.0 °C · 5 = K -200 to 1300 °C · 6 = K -20.0 to 500.0 °C · 7 = J -100 to 850 °C · 8 = J -20.0 to 400.0 °C · 9 = T -200 to 400 °C · 10 = T -199.9 to 400.0 °C · 11 = E -200 to 600 °C · 12 = L -100 to 850 °C · 13 = U -200 to 400 °C · 14 = U -199.9 to 400.0 °C · 15 = N -200 to 1300 °C · 16 = R 0 to 1700 °C · 17 = S 0 to 1700 °C · 18 = B 100 to 1800 °C · 19 = W 0 to 2300 °C · 20 = PLII 0 to 1300 °C · 21 = Infrared sensor K 140 °F/60 °C · 22 = Infrared sensor K 240 °F/120 °C · 23 = Infrared sensor K 280 °F/140 °C · 24 = Infrared sensor K 440 °F/220 °C · 25 = 4-20 mA · 26 = 0-20 mA · 27 = 1-5 V · 28 = 0-5 V · 29 = 0-10 V · 30 = 0-50 mV (E5CC-U version 2.2 or later only)
5-7 (PDF 101)
2C0111265 (0x2C01)HRTemperature unitU16R/W03·06·10
0 = °C · 1 = °F
5-7 (PDF 101)
2D0F11535 (0x2D0F)HRSP upper limitS16R/W03·06·10
Integer without decimal point; decimal places follow 2410h (decimal point monitor) / input type
5-7 (PDF 101)
2D1011536 (0x2D10)HRSP lower limitS16R/W03·06·10
Integer without decimal point; decimal places follow 2410h (decimal point monitor) / input type
5-7 (PDF 101)

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).

Download JSON

Sources