An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 9600 bps — options: 9600, 19200, 38400, 57600 |
| Data · parity · stop | 8 · Even · 1 |
| Slave ID (factory) | 1 (1~99) |
| Max per request | 106 registers |
| Manual address style | Wire address as is (0-based) |
- Addressing: the read example (4-9 (PDF 87)) sends 01 03 20 00 00 01 8F CA to read PV (2000h) and gets 01 03 02 03 E8 B8 FA (100.0 °C). The write example (4-12) 01 10 21 05 00 02 04 03 E8 FC 18 66 BB writes 1000/-1000 to 2105h/2106h; the operation command example (4-14) is 01 06 00 00 01 01 49 9A (stop). Manual address = frame address (0-based). CRCs match calculation.
- Factory protocol is CompoWay/F: set PSEL to Mod in the communications setting level and reset. Defaults: unit 1, 9600 bps, even parity. In Modbus the data length is 8 bits and stop bits are fixed to 1 with parity, 2 without (1-6 (PDF 28)).
- Function codes 03, 06, 08, 10. Two-byte mode (this table): up to 106 read / 104 write per request. Four-byte mode uses different addresses from 0000h (two words per value). Turn Communications Writing ON first (operation command 0001h) to write parameters.
Registers (26)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 0000 | 0 (0x0000) | HR | Operation command | U16 | W | 06 | FC06 only. Value = command code (high byte) + related information (low byte), e.g. STOP = 0101h. Manual example: 01 06 00 00 01 01 49 9A. Multi-SP (02xx), alarm latch cancel (0Cxx) etc. in the table on pp.2-16 to 2-17 0 = Communications writing OFF · 1 = Communications writing ON · 256 = Run · 257 = Stop · 768 = AT cancel · 769 = 100% AT execute · 770 = 40% AT execute · 1024 = Backup mode · 1025 = RAM write mode · 1280 = Save RAM data · 1536 = Software reset · 1792 = Move to setup area 1 · 2048 = Move to protect level · 2304 = Automatic mode · 2305 = Manual mode · 2816 = Parameter initialization 4-12, 4-14 (PDF 90, 92) | |
| 2000 | 8192 (0x2000) | HR | PV (process value) | S16 | R | 03 | Integer without decimal point, e.g. 100.0 °C = 03E8h (manual read example) 5-2 (PDF 96) | |
| 2001 | 8193 (0x2001) | HR | Status (lower 16 bits) | U16 | R | 03 | 1 = generated/ON b0 Heater overcurrent (CT1) · b1 Heater current hold (CT1) · b2 A/D converter error · b3 HS alarm (CT1) · b4 RSP input error · b6 Input error · b7 Potentiometer input error · b8 Control output (heating)/open output · b9 Control output (cooling)/close output · b10 HB alarm (CT1) · b11 HB alarm (CT2) · b12 Alarm 1 · b13 Alarm 2 · b14 Alarm 3 · b15 Program end output 5-2, 3-25 (PDF 96, 77) | |
| 2002 | 8194 (0x2002) | HR | Internal set point | S16 | R | 03 | Integer without decimal point; decimal places follow 2410h (decimal point monitor) / input type 5-2 (PDF 96) | |
| 2003 | 8195 (0x2003) | HR | Heater current 1 value monitor | U16 | ×0.1 A | R | 03 | Range 0 ~ 55 A 5-2 (PDF 96) |
| 2004 | 8196 (0x2004) | HR | MV monitor (heating) | S16 | ×0.1 % | R | 03 | Range -5 ~ 105 % 5-2 (PDF 96) |
| 2005 | 8197 (0x2005) | HR | MV monitor (cooling) | U16 | ×0.1 % | R | 03 | Range 0 ~ 105 % 5-2 (PDF 96) |
| 2103 | 8451 (0x2103) | HR | Set point | S16 | R/W | 03·06·10 | Integer without decimal point; decimal places follow 2410h (decimal point monitor) / input type 5-2 (PDF 96) | |
| 2104 | 8452 (0x2104) | HR | Alarm value 1 | S16 | R/W | 03·06·10 | Decimal point follows the input setting Range -1999 ~ 9999 5-2 (PDF 96) | |
| 2105 | 8453 (0x2105) | HR | Alarm value upper limit 1 | S16 | R/W | 03·06·10 | Decimal point follows the input setting Range -1999 ~ 9999 5-2 (PDF 96) | |
| 2106 | 8454 (0x2106) | HR | Alarm value lower limit 1 | S16 | R/W | 03·06·10 | Decimal point follows the input setting Range -1999 ~ 9999 5-2 (PDF 96) | |
| 2107 | 8455 (0x2107) | HR | Alarm value 2 | S16 | R/W | 03·06·10 | Decimal point follows the input setting Range -1999 ~ 9999 5-2 (PDF 96) | |
| 2108 | 8456 (0x2108) | HR | Alarm value upper limit 2 | S16 | R/W | 03·06·10 | Decimal point follows the input setting Range -1999 ~ 9999 5-2 (PDF 96) | |
| 2109 | 8457 (0x2109) | HR | Alarm value lower limit 2 | S16 | R/W | 03·06·10 | Decimal point follows the input setting Range -1999 ~ 9999 5-2 (PDF 96) | |
| 2404 | 9220 (0x2404) | HR | Multi-SP No. monitor | U16 | R | 03 | Range 0 ~ 7 5-2 (PDF 96) | |
| 2407 | 9223 (0x2407) | HR | Status (upper 16 bits) | U16 | R | 03 | Bits 16-31 of the 32-bit status, read as bits 0-15 b0 Event input 1 · b1 Event input 2 · b2 Event input 3 · b3 Event input 4 · b4 Write mode (0 backup / 1 RAM write) · b5 Non-volatile memory (1 = RAM differs) · b6 Setup area (0 = area 0 / 1 = area 1) · b7 AT in progress · b8 RUN/STOP (0 = run / 1 = stop) · b9 Communications writing enabled · b10 Auto/manual (1 = manual) · b11 Program start · b12 Heater overcurrent (CT2) · b13 Heater current hold (CT2) · b15 HS alarm (CT2) 5-2, 3-25 (PDF 96, 77) | |
| 2410 | 9232 (0x2410) | HR | Decimal point monitor | U16 | R | 03 | Number of decimal places Range 0 ~ 3 5-2 (PDF 96) | |
| 2A00 | 10752 (0x2A00) | HR | Proportional band | U16 | ×0.1 | R/W | 03·06·10 | Range 0.1 ~ 999.9 5-6 (PDF 100) |
| 2A01 | 10753 (0x2A01) | HR | Integral time | U16 | s | R/W | 03·06·10 | 1 s (0-9999) or 0.1 s (0.0-999.9) depending on the integral/derivative time unit setting 5-6 (PDF 100) |
| 2A02 | 10754 (0x2A02) | HR | Derivative time | U16 | s | R/W | 03·06·10 | Unit as for the integral time 5-6 (PDF 100) |
| 2A05 | 10757 (0x2A05) | HR | MV upper limit | S16 | ×0.1 % | R/W | 03·06·10 | 5-6 (PDF 100) |
| 2A06 | 10758 (0x2A06) | HR | MV lower limit | S16 | ×0.1 % | R/W | 03·06·10 | 5-6 (PDF 100) |
| 2C00 | 11264 (0x2C00) | HR | Input type | U16 | R/W | 03·06·10 | Initial setting level: move to setup area 1 (operation command 0700h) to write. °F ranges in the manual table 0 = Pt100 -200 to 850 °C · 1 = Pt100 -199.9 to 500.0 °C · 2 = Pt100 0.0 to 100.0 °C · 3 = JPt100 -199.9 to 500.0 °C · 4 = JPt100 0.0 to 100.0 °C · 5 = K -200 to 1300 °C · 6 = K -20.0 to 500.0 °C · 7 = J -100 to 850 °C · 8 = J -20.0 to 400.0 °C · 9 = T -200 to 400 °C · 10 = T -199.9 to 400.0 °C · 11 = E -200 to 600 °C · 12 = L -100 to 850 °C · 13 = U -200 to 400 °C · 14 = U -199.9 to 400.0 °C · 15 = N -200 to 1300 °C · 16 = R 0 to 1700 °C · 17 = S 0 to 1700 °C · 18 = B 100 to 1800 °C · 19 = W 0 to 2300 °C · 20 = PLII 0 to 1300 °C · 21 = Infrared sensor K 140 °F/60 °C · 22 = Infrared sensor K 240 °F/120 °C · 23 = Infrared sensor K 280 °F/140 °C · 24 = Infrared sensor K 440 °F/220 °C · 25 = 4-20 mA · 26 = 0-20 mA · 27 = 1-5 V · 28 = 0-5 V · 29 = 0-10 V · 30 = 0-50 mV (E5CC-U version 2.2 or later only) 5-7 (PDF 101) | |
| 2C01 | 11265 (0x2C01) | HR | Temperature unit | U16 | R/W | 03·06·10 | 0 = °C · 1 = °F 5-7 (PDF 101) | |
| 2D0F | 11535 (0x2D0F) | HR | SP upper limit | S16 | R/W | 03·06·10 | Integer without decimal point; decimal places follow 2410h (decimal point monitor) / input type 5-7 (PDF 101) | |
| 2D10 | 11536 (0x2D10) | HR | SP lower limit | S16 | R/W | 03·06·10 | Integer without decimal point; decimal places follow 2410h (decimal point monitor) / input type 5-7 (PDF 101) |
Notes
- Values are integers without decimal point (e.g. 100.0 → 1000). PV, SP and alarm decimal places follow the input type / decimal point setting, so no scale is given.
- Only models with RS-485 communications. Output, alarm and heater current items depend on the model options.
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- omron/e5cc.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- E5□C Digital Temperature Controllers Communications Manual — OMRON Corporation, Cat. No. H175-E1-17 · Communications settings 1-6 (PDF 28), operation commands 2-16 to 2-17 (PDF 46-47), status 3-23 to 3-25 (PDF 75-77), Modbus procedure 4-1 to 4-15 (PDF 79-93), variable list 5-2 to 5-7 (PDF 96-101) · checked 2026-10-23