An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 38400 bps — options: 9600, 19200, 38400 |
| Data · parity · stop | 8 · Odd · 1 |
| Slave ID (factory) | 1 (1~255) |
| 32-bit order | CDAB |
| Max per request | 32 registers |
| Manual address style | 40001/30001 style (wire address + 1, first digit = table) |
- Addressing: frame address = lower four digits of the number − 1 (printed p.9). Examples: 01 03 08 30 00 02 C6 64 (42097 PV1F), 01 04 01 02 00 02 D1 F7 (30259 PV1), 01 06 02 82 03 E8 28 E4 and 01 10 02 82 00 06 … B6 D8 (40643 P1-), replies 01 03 04 0F A0 00 00 F9 05, 01 04 04 38 80 00 01 36 CC, 01 10 02 82 00 06 E1 9B (printed pp.18-23). All CRCs match calculation.
- All data is two words with the low word sent first (99999 = 86 9F 00 01, printed p.17). 06h can write only the low word (printed p.12). Functions 03, 04, 06 and 10h; up to 32 words for 03h/10h, 15 for 04h.
- Defaults (printed p.6): RS-485 38400 bps, 8 data bits, 1 stop bit, odd parity, station 1 (STN4 0-255, 0 stops communication). Cycle power after changing. The PC loader port is fixed at station 1.
Registers (17)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 30257 | 256 (0x0100) | IR | Control mode status (MODE1) | S32 CDAB | R | 04 | b0 Fault · b1 Standby · b2 Remote ack · b3 Other than auto · b4 Auto mode request · b5 Remote mode request · b6 Auto-tuning · b7 Normal operation · b8 PV tracking · b9 Local SV · b10 Remote SV · b11 Local + PV tracking · b12 Forced manual · b13 EX-MV · b14 Manual mode printed p.49 (PDF p.52) | |
| 30259 | 258 (0x0102) | IR | PV1 (process value used for control) | S32 CDAB | R | 04 | Manual example 01 04 01 02 00 02 D1 F7 → 38 80 00 01 = 00013880h = 80000 (PV1D = 2 → 800.00 °C), reply CRC 36 CC. On input error, 105 % or −5 % of the range printed p.20 (PDF p.23), printed p.28 (PDF p.31), printed p.49 (PDF p.52) | |
| 30261 | 260 (0x0104) | IR | SV1 (setpoint in use) | S32 CDAB | R | 04 | Engineering-unit integer; decimal places from PV1D (42101) or UCD1, depending on control type TPLT printed p.28 (PDF p.31), printed p.49 (PDF p.52) | |
| 30263 | 262 (0x0106) | IR | DV1 (deviation in use) | S32 CDAB | R | 04 | Engineering-unit integer; decimal places from PV1D (42101) or UCD1, depending on control type TPLT printed p.28 (PDF p.31), printed p.49 (PDF p.52) | |
| 30265 | 264 (0x0108) | IR | MV1 (manipulated value in use) | S32 CDAB | ×0.1 % | R | 04 | Range -25 ~ 125 % printed p.28 (PDF p.31), printed p.49 (PDF p.52) |
| 30269 | 268 (0x010C) | IR | FAULT1 (input error status) | S32 CDAB | R | 04 | 0 = Normal · 1 = Over · 2 = Under printed p.28 (PDF p.31), printed p.49 (PDF p.52) | |
| 40021 | 20 (0x0014) | HR | AT (auto-tuning command) | S32 CDAB | R/W | 03·10 | 0 = Write: stop AT / read: not active · 1 = Write: execute AT / read: active printed p.30 (PDF p.33) | |
| 40033 | 32 (0x0020) | HR | LACH (alarm unlatch) | S32 CDAB | R/W | 03·10 | 0 = Write: no effect / read: latched · 1 = Write: unlatch / read: unlatched printed p.30 (PDF p.33) | |
| 40097 | 96 (0x0060) | HR | RES (reset command) | S32 CDAB | R/W | 03·10 | Write 1 instead of cycling power after changing the input range (printed p.24) 0 = Write: no effect / read: operating normally · 1 = Write: execute reset / read: being reset printed p.24 (PDF p.27), printed p.30 (PDF p.33) | |
| 40641 | 640 (0x0280) | HR | SV_L1 (local SV) | S32 CDAB | R/W | 03·10 | Engineering-unit integer; decimal places from PV1D (42101) or UCD1, depending on control type TPLT printed p.25 (PDF p.28), printed p.31 (PDF p.34) | |
| 40643 | 642 (0x0282) | HR | P1 (proportional band) | S32 CDAB | ×0.1 % | R/W | 03·10 | Manual examples 01 06 02 82 03 E8 28 E4 (100.0; 06h writes the low word only), 01 10 02 82 00 06 0C 03 E8 00 00 00 64 00 00 00 32 00 00 B6 D8 (P1, I1, D1) Range 0 ~ 999.9 % printed p.21~23 (PDF p.24~26), printed p.31 (PDF p.34) |
| 40645 | 644 (0x0284) | HR | I1 (integral time) | S32 CDAB | ×0.1 s | R/W | 03·10 | Range 0 ~ 3200 s printed p.31 (PDF p.34) |
| 40647 | 646 (0x0286) | HR | D1 (derivative time) | S32 CDAB | ×0.1 s | R/W | 03·10 | Range 0 ~ 999.9 s printed p.31 (PDF p.34) |
| 42097 | 2096 (0x0830) | HR | PV1F (PV1 full scale) | S32 CDAB | R/W | 03·10 | Manual example 01 03 08 30 00 02 C6 64 → 0F A0 00 00 = 4000, reply CRC F9 05. After changing, FIX and reset (or power cycle) printed p.18 (PDF p.21), printed p.24 (PDF p.27), printed p.39 (PDF p.42) | |
| 42099 | 2098 (0x0832) | HR | PV1B (PV1 base scale) | S32 CDAB | R/W | 03·10 | printed p.39 (PDF p.42) | |
| 42101 | 2100 (0x0834) | HR | PV1D (PV1 decimal point position) | S32 CDAB | R/W | 03·10 | Changing it updates PV1F and PV1B automatically (e.g. 0-400 → 0.0-400.0) Range 0 ~ 3 printed p.24 (PDF p.27), printed p.39 (PDF p.42) | |
| 43153 | 3152 (0x0C50) | HR | FIX command (save to non-volatile memory) | S32 CDAB | R/W | 03·10 | Procedure (Fig. 5-4): read 0 with 03h → write 1 with 06h → read until 0. Takes 5 s to 3 min; do not power off meanwhile. 100,000-write limit 0 = Read: no FIX (finished) · 1 = Write: execute FIX printed p.16 (PDF p.19), printed p.43 (PDF p.46) |
Notes
- The address map (printed pp.30-50) has text columns shifted line by line in the PDF, so only items whose names could be matched by frame examples, the decimal point tables (printed pp.25-28) or the text are included. Alarm settings (40257-), palettes, ramp/soak etc. are left out.
- Without FIX, values written over communication are lost at power-off (printed p.16). Page numbers are printed pages (PDF = printed + 3).
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- fuji-electric/pxh.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.