An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 9600 bps — options: 2400, 4800, 9600, 19200, 38400 |
| Data · parity · stop | 8 · None · 2 |
| Slave ID (factory) | 1 (1~127) |
| Manual address style | Wire address as is (0-based) |
- The manual writes «400001 (0000)»: 1-based reference number plus hex communication address in parentheses. Each table starts at (0000), so the parenthesized value is used as the 0-based wire address (comm manual pp.23-40). Frame examples (pp.12-20) show layout only, no numbers.
- Defaults: ADRS 1 (1-127), BPS 9600, PRTY NONE, STP 2 bits, response wait 20 ms (comm manual pp.37-38). 8 data bits fixed and speed list from the user manual p.89. RS485 only on communication option models.
Registers (41)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 000001 (0000) | 0 (0x0000) | CO | Control output RUN/STOP | BIT | R/W | 01·05 | 0 = RUN (default) · 1 = STOP p.23 | |
| 000002 (0001) | 1 (0x0001) | CO | Auto-tuning run/stop | BIT | R/W | 01·05 | 0 = OFF · 1 = ON p.23 | |
| 100004 (0003) | 3 (0x0003) | DI | OUT1 lamp | BIT | R | 02 | p.24 | |
| 100005 (0004) | 4 (0x0004) | DI | OUT2 lamp | BIT | R | 02 | p.24 | |
| 100006 (0005) | 5 (0x0005) | DI | AT lamp | BIT | R | 02 | p.24 | |
| 100010 (0009) | 9 (0x0009) | DI | Alarm 1 lamp | BIT | R | 02 | p.24 | |
| 100011 (000A) | 10 (0x000A) | DI | Alarm 2 lamp | BIT | R | 02 | p.24 | |
| 100012 (000B) | 11 (0x000B) | DI | Alarm 3 lamp | BIT | R | 02 | p.24 | |
| 100013 (000C) | 12 (0x000C) | DI | Manual control lamp | BIT | R | 02 | p.24 | |
| 100014 (000D) | 13 (0x000D) | DI | DI-1 input | BIT | R | 02 | p.24 | |
| 100015 (000E) | 14 (0x000E) | DI | DI-2 input | BIT | R | 02 | p.24 | |
| 300104 (0067) | 103 (0x0067) | IR | Software version | U16 | R | 04 | p.25 | |
| 301001 (03E8) | 1000 (0x03E8) | IR | Present value (PV) | S16 | R | 04 | Decimals follow the input type (input register 301002 decimal point), so no fixed scale Range -1999 ~ 9999 p.25 | |
| 301002 (03E9) | 1001 (0x03E9) | IR | Decimal point position | U16 | R | 04 | 0 = 0 · 1 = 0.0 · 2 = 0.00 · 3 = 0.000 p.25 | |
| 301003 (03EA) | 1002 (0x03EA) | IR | Display unit | U16 | R | 04 | 0 = °C · 1 = °F · 2 = % · 3 = OFF p.26 | |
| 301004 (03EB) | 1003 (0x03EB) | IR | Set value (SV) | S16 | R | 04 | Decimals follow the input type (input register 301002 decimal point), so no fixed scale p.26 | |
| 301005 (03EC) | 1004 (0x03EC) | IR | Heating MV | U16 | ×0.1 % | R | 04 | Range 0 ~ 100 % p.26 |
| 301006 (03ED) | 1005 (0x03ED) | IR | Cooling MV | U16 | ×0.1 % | R | 04 | Range 0 ~ 100 % p.26 |
| 301008 (03EF) | 1007 (0x03EF) | IR | Heater current | U16 | ×0.1 A | R | 04 | Range 0 ~ 50 A p.27 |
| 400001 (0000) | 0 (0x0000) | HR | Set value (SV) | S16 | R/W | 03·06·10 | Within L-SV to H-SV. Decimals follow the input type (input register 301002 decimal point), so no fixed scale p.29 | |
| 400004 (0003) | 3 (0x0003) | HR | Auto/manual control | U16 | R/W | 03·06·10 | 0 = AUTO (default) · 1 = MAN p.29 | |
| 400051 (0032) | 50 (0x0032) | HR | R-S control output RUN/STOP | U16 | R/W | 03·06·10 | 0 = RUN (default) · 1 = STOP p.30 | |
| 400052 (0033) | 51 (0x0033) | HR | SV-N multi-SV number | U16 | R/W | 03·06·10 | 0 = SV-0 (default) · 1 = SV-1 · 2 = SV-2 · 3 = SV-3 p.30 | |
| 400054 (0035) | 53 (0x0035) | HR | AL1.L alarm 1 low-limit set value | S16 | R/W | 03·06·10 | Decimals follow the input type (input register 301002 decimal point), so no fixed scale p.30 | |
| 400055 (0036) | 54 (0x0036) | HR | AL1.H alarm 1 high-limit set value | S16 | R/W | 03·06·10 | Decimals follow the input type (input register 301002 decimal point), so no fixed scale p.30 | |
| 400060 (003B) | 59 (0x003B) | HR | SV-0 set value | S16 | R/W | 03·06·10 | Decimals follow the input type (input register 301002 decimal point), so no fixed scale p.30 | |
| 400101 (0064) | 100 (0x0064) | HR | AT auto-tuning | U16 | R/W | 03·06·10 | 0 = OFF (default) · 1 = ON p.32 | |
| 400102 (0065) | 101 (0x0065) | HR | H-P heating proportional band | U16 | ×0.1 | R/W | 03·06·10 | Unit °C/°F/%; default 10.0 Range 0.1 ~ 999.9 p.32 |
| 400104 (0067) | 103 (0x0067) | HR | H-I heating integral time | U16 | s | R/W | 03·06·10 | Range 0 ~ 9999 s p.32 |
| 400106 (0069) | 105 (0x0069) | HR | H-D heating derivative time | U16 | s | R/W | 03·06·10 | Range 0 ~ 9999 s p.32 |
| 400151 (0096) | 150 (0x0096) | HR | IN-T input type | U16 | R/W | 03·06·10 | See the input type table; default 0 (TCK.1) p.34 | |
| 400152 (0097) | 151 (0x0097) | HR | UNIT temperature unit | U16 | R/W | 03·06·10 | 0 = °C (default) · 1 = °F p.34 | |
| 400159 (009E) | 158 (0x009E) | HR | IN-B input correction | S16 | R/W | 03·06·10 | Decimals follow the input type (input register 301002 decimal point), so no fixed scale p.34 | |
| 400160 (009F) | 159 (0x009F) | HR | MAV.F input digital filter | U16 | ×0.1 s | R/W | 03·06·10 | Range 0.1 ~ 120 s p.34 |
| 400161 (00A0) | 160 (0x00A0) | HR | L-SV SV low limit | S16 | R/W | 03·06·10 | Decimals follow the input type (input register 301002 decimal point), so no fixed scale p.34 | |
| 400162 (00A1) | 161 (0x00A1) | HR | H-SV SV high limit | S16 | R/W | 03·06·10 | Decimals follow the input type (input register 301002 decimal point), so no fixed scale p.34 | |
| 400225 (00E0) | 224 (0x00E0) | HR | ADRS communication address | U16 | R/W | 03·06·10 | Range 1 ~ 127 p.37 | |
| 400226 (00E1) | 225 (0x00E1) | HR | BPS communication speed | U16 | R/W | 03·06·10 | 0 = 2400 bps · 1 = 4800 bps · 2 = 9600 bps (default) · 3 = 19200 bps · 4 = 38400 bps p.38 | |
| 400227 (00E2) | 226 (0x00E2) | HR | PRTY parity | U16 | R/W | 03·06·10 | 0 = NONE (default) · 1 = EVEN · 2 = ODD p.38 | |
| 400228 (00E3) | 227 (0x00E3) | HR | STP stop bit | U16 | R/W | 03·06·10 | 0 = 1 bit · 1 = 2 bits (default) p.38 | |
| 400230 (00E5) | 229 (0x00E5) | HR | COMW communication write | U16 | R/W | 03·06·10 | 0 = EN.A enabled (default) · 1 = DIS.A disabled p.38 |
Notes
- Temperature-type values (PV, SV, alarms, correction, SV limits) have input-dependent decimals, so no scale. 301007 (front display bit field, p.28) is left out. Setting COMW to DIS.A blocks communication writes (exception 04).
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- autonics/kpn.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- KPN Series Communication Manual MCT-KPNC1-V1.0_EN — Autonics, MCT-KPNC1-V1.0_EN · pp.11-21 Modbus RTU, pp.23-40 mapping table (printed page = PDF page) · checked 2026-10-31
- User Manual Temperature Controller KPN Series (KPN_EN_AUM-E-0301-AF) — Autonics, AUM-E-0301-AF (2024-11-27) · pp.89-90 communication specification · checked 2026-10-31