Autonics KPN Series Modbus register map

Modbus RTU. Coils (RUN/STOP, AT), discrete inputs (lamps, DI), input registers (PV, SV, MV), holding registers (settings, FC 03/06/16). · Temperature controller

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)9600 bps — options: 2400, 4800, 9600, 19200, 38400
Data · parity · stop8 · None · 2
Slave ID (factory)1 (1~127)
Manual address styleWire address as is (0-based)

Registers (41)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

41

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
000001 (0000)0 (0x0000)COControl output RUN/STOPBITR/W01·05
0 = RUN (default) · 1 = STOP
p.23
000002 (0001)1 (0x0001)COAuto-tuning run/stopBITR/W01·05
0 = OFF · 1 = ON
p.23
100004 (0003)3 (0x0003)DIOUT1 lampBITR02
p.24
100005 (0004)4 (0x0004)DIOUT2 lampBITR02
p.24
100006 (0005)5 (0x0005)DIAT lampBITR02
p.24
100010 (0009)9 (0x0009)DIAlarm 1 lampBITR02
p.24
100011 (000A)10 (0x000A)DIAlarm 2 lampBITR02
p.24
100012 (000B)11 (0x000B)DIAlarm 3 lampBITR02
p.24
100013 (000C)12 (0x000C)DIManual control lampBITR02
p.24
100014 (000D)13 (0x000D)DIDI-1 inputBITR02
p.24
100015 (000E)14 (0x000E)DIDI-2 inputBITR02
p.24
300104 (0067)103 (0x0067)IRSoftware versionU16R04
p.25
301001 (03E8)1000 (0x03E8)IRPresent value (PV)S16R04
Decimals follow the input type (input register 301002 decimal point), so no fixed scale
Range -1999 ~ 9999
p.25
301002 (03E9)1001 (0x03E9)IRDecimal point positionU16R04
0 = 0 · 1 = 0.0 · 2 = 0.00 · 3 = 0.000
p.25
301003 (03EA)1002 (0x03EA)IRDisplay unitU16R04
0 = °C · 1 = °F · 2 = % · 3 = OFF
p.26
301004 (03EB)1003 (0x03EB)IRSet value (SV)S16R04
Decimals follow the input type (input register 301002 decimal point), so no fixed scale
p.26
301005 (03EC)1004 (0x03EC)IRHeating MVU16×0.1 %R04
Range 0 ~ 100 %
p.26
301006 (03ED)1005 (0x03ED)IRCooling MVU16×0.1 %R04
Range 0 ~ 100 %
p.26
301008 (03EF)1007 (0x03EF)IRHeater currentU16×0.1 AR04
Range 0 ~ 50 A
p.27
400001 (0000)0 (0x0000)HRSet value (SV)S16R/W03·06·10
Within L-SV to H-SV. Decimals follow the input type (input register 301002 decimal point), so no fixed scale
p.29
400004 (0003)3 (0x0003)HRAuto/manual controlU16R/W03·06·10
0 = AUTO (default) · 1 = MAN
p.29
400051 (0032)50 (0x0032)HRR-S control output RUN/STOPU16R/W03·06·10
0 = RUN (default) · 1 = STOP
p.30
400052 (0033)51 (0x0033)HRSV-N multi-SV numberU16R/W03·06·10
0 = SV-0 (default) · 1 = SV-1 · 2 = SV-2 · 3 = SV-3
p.30
400054 (0035)53 (0x0035)HRAL1.L alarm 1 low-limit set valueS16R/W03·06·10
Decimals follow the input type (input register 301002 decimal point), so no fixed scale
p.30
400055 (0036)54 (0x0036)HRAL1.H alarm 1 high-limit set valueS16R/W03·06·10
Decimals follow the input type (input register 301002 decimal point), so no fixed scale
p.30
400060 (003B)59 (0x003B)HRSV-0 set valueS16R/W03·06·10
Decimals follow the input type (input register 301002 decimal point), so no fixed scale
p.30
400101 (0064)100 (0x0064)HRAT auto-tuningU16R/W03·06·10
0 = OFF (default) · 1 = ON
p.32
400102 (0065)101 (0x0065)HRH-P heating proportional bandU16×0.1R/W03·06·10
Unit °C/°F/%; default 10.0
Range 0.1 ~ 999.9
p.32
400104 (0067)103 (0x0067)HRH-I heating integral timeU16sR/W03·06·10
Range 0 ~ 9999 s
p.32
400106 (0069)105 (0x0069)HRH-D heating derivative timeU16sR/W03·06·10
Range 0 ~ 9999 s
p.32
400151 (0096)150 (0x0096)HRIN-T input typeU16R/W03·06·10
See the input type table; default 0 (TCK.1)
p.34
400152 (0097)151 (0x0097)HRUNIT temperature unitU16R/W03·06·10
0 = °C (default) · 1 = °F
p.34
400159 (009E)158 (0x009E)HRIN-B input correctionS16R/W03·06·10
Decimals follow the input type (input register 301002 decimal point), so no fixed scale
p.34
400160 (009F)159 (0x009F)HRMAV.F input digital filterU16×0.1 sR/W03·06·10
Range 0.1 ~ 120 s
p.34
400161 (00A0)160 (0x00A0)HRL-SV SV low limitS16R/W03·06·10
Decimals follow the input type (input register 301002 decimal point), so no fixed scale
p.34
400162 (00A1)161 (0x00A1)HRH-SV SV high limitS16R/W03·06·10
Decimals follow the input type (input register 301002 decimal point), so no fixed scale
p.34
400225 (00E0)224 (0x00E0)HRADRS communication addressU16R/W03·06·10
Range 1 ~ 127
p.37
400226 (00E1)225 (0x00E1)HRBPS communication speedU16R/W03·06·10
0 = 2400 bps · 1 = 4800 bps · 2 = 9600 bps (default) · 3 = 19200 bps · 4 = 38400 bps
p.38
400227 (00E2)226 (0x00E2)HRPRTY parityU16R/W03·06·10
0 = NONE (default) · 1 = EVEN · 2 = ODD
p.38
400228 (00E3)227 (0x00E3)HRSTP stop bitU16R/W03·06·10
0 = 1 bit · 1 = 2 bits (default)
p.38
400230 (00E5)229 (0x00E5)HRCOMW communication writeU16R/W03·06·10
0 = EN.A enabled (default) · 1 = DIS.A disabled
p.38

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).

Download JSON

Sources