An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 9600 bps — options: 9600 |
| Data · parity · stop | 8 · Odd · 1 |
| Max per request | 60 registers |
| Manual address style | 40001/30001 style (wire address + 1, first digit = table) |
- Addressing: frame address = lower four digits of the number − 1 (printed p.8). Examples: 01 01 00 00 00 01 FD CA (coil 00001), 1F 02 00 0C 00 02 3A 76 (10013-), 02 03 00 1E 00 02 A4 3E (40031-), 02 03 04 06 00 02 25 09 (41031-), 01 04 00 00 00 01 31 CA (30001), 01 04 03 E8 00 01 B1 BA (31001), 01 05 00 00 FF 00 8C 3A, 01 06 00 05 03 E8 99 75 (40006), 01 10 00 05 00 03 06 03 E8 00 64 00 32 56 BE (printed pp.16-27). Request and reply CRCs match calculation, except the last 31001 reply (01 04 02 01 4F), which repeats 38 32 from the previous example (calculated F9 54).
- Communication (printed p.5): 9600 bps, 8 data bits and 1 stop bit fixed; parity CoM default 0 = odd (1 even, 2 none); station STno 0-255 (0 stops communication); protocol PCoL = 1 (Modbus). Functions 01, 02, 03, 04, 05, 06 and 10h; up to 60 words for 03h/10h and 37 for 04h (printed p.11).
Registers (40)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 00001 | 0 (0x0000) | CO | FIX (save settings to non-volatile memory) | BIT | R/W | 01·05 | 1 = request. Manual example 01 05 00 00 FF 00 8C 3A. Saving takes about 5 s; do not power off meanwhile printed p.24 (PDF p.27), printed p.31 (PDF p.34) | |
| 10001 | 0 (0x0000) | DI | Alarm 1 ON/OFF | BIT | R | 02 | printed p.37 (PDF p.40) | |
| 10005 | 4 (0x0004) | DI | Alarm 2 ON/OFF | BIT | R | 02 | printed p.37 (PDF p.40) | |
| 10009 | 8 (0x0008) | DI | Alarm 1 output (de-energizing alarm result) | BIT | R | 02 | printed p.37 (PDF p.40) | |
| 10010 | 9 (0x0009) | DI | Alarm 2 output | BIT | R | 02 | printed p.37 (PDF p.40) | |
| 10011 | 10 (0x000A) | DI | Alarm 3 output | BIT | R | 02 | printed p.37 (PDF p.40) | |
| 10012 | 11 (0x000B) | DI | HB (heater break) alarm relay output | BIT | R | 02 | printed p.37 (PDF p.40) | |
| 10013 | 12 (0x000C) | DI | Alarm 1 ON/OFF (same as 10001) | BIT | R | 02 | Manual example: 1F 02 00 0C 00 02 3A 76 → 01h (alarm 1 ON, alarm 2 OFF) printed p.18 (PDF p.21), printed p.37 (PDF p.40) | |
| 10014 | 13 (0x000D) | DI | Alarm 2 ON/OFF | BIT | R | 02 | printed p.37 (PDF p.40) | |
| 10015 | 14 (0x000E) | DI | Alarm 3 ON/OFF | BIT | R | 02 | printed p.37 (PDF p.40) | |
| 30001 | 0 (0x0000) | IR | PV (internal value, %FS) | S16 | ×0.01 % | R | 04 | % of input range (0.00-100.00 %FS). Manual example 01 04 00 00 00 01 31 CA → 0346h = 8.38 %FS (33.5 °C on a 0-400 °C range) printed p.22 (PDF p.25), printed p.36 (PDF p.39) |
| 31001 | 1000 (0x03E8) | IR | PV (engineering units) | S16 | R | 04 | Manual example 01 04 03 E8 00 01 B1 BA → 014Fh = 335 (1 decimal → 33.5 °C). On input error, 105 % or −5 % of the range printed p.23 (PDF p.26), printed p.42 (PDF p.45) | |
| 31002 | 1001 (0x03E9) | IR | SV in use | S16 | R | 04 | May differ from 40003/41003 (front-panel SV) during ramp/soak or SV switching; monitor this one printed p.42 (PDF p.45) | |
| 31003 | 1002 (0x03EA) | IR | Deviation DV in use | S16 | R | 04 | Engineering units (scaled to the input range), integer without decimal point; decimal places from 41020 (P-dP) printed p.42 (PDF p.45) | |
| 31004 | 1003 (0x03EB) | IR | MV (output 1) | S16 | ×0.01 % | R | 04 | Range -3 ~ 103 % printed p.42 (PDF p.45) |
| 31005 | 1004 (0x03EC) | IR | MV (output 2) | S16 | ×0.01 % | R | 04 | Range -3 ~ 103 % printed p.42 (PDF p.45) |
| 31006 | 1005 (0x03ED) | IR | Station number | U16 | R | 04 | printed p.42 (PDF p.45) | |
| 31007 | 1006 (0x03EE) | IR | Alarm status | U16 | R | 04 | b0 Alarm 1 output · b1 Alarm 2 output · b2 Alarm 3 output · b3 HB alarm relay output · b4 Alarm 1 ON · b5 Alarm 2 ON · b6 Alarm 3 ON · b7 HB alarm output printed p.42 (PDF p.45), printed p.44 (PDF p.47) | |
| 31008 | 1007 (0x03EF) | IR | Input/main unit abnormal status | U16 | R | 04 | b0 Input lower open circuit · b1 Input upper open circuit · b2 Input under-range · b3 Input over-range · b6 Setting range error · b7 EEPROM error printed p.42 (PDF p.45), printed p.44 (PDF p.47) | |
| 31009 | 1008 (0x03F0) | IR | Ramp/soak current position | U16 | R | 04 | Range 0 ~ 17 printed p.42 (PDF p.45), printed p.45 (PDF p.48) | |
| 31010 | 1009 (0x03F1) | IR | Heater current | U16 | ×0.1 A | R | 04 | Range 0 ~ 50 A printed p.42 (PDF p.45) |
| 41003 | 1002 (0x03EA) | HR | SV (front-panel set value) | S16 | R/W | 03·06·10 | Engineering units (scaled to the input range), integer without decimal point; decimal places from 41020 (P-dP) printed p.38 (PDF p.41) | |
| 41004 | 1003 (0x03EB) | HR | Control RUN/standby | U16 | R/W | 03·06·10 | 0 = RUN (standby off) · 1 = Standby printed p.38 (PDF p.41) | |
| 41005 | 1004 (0x03EC) | HR | Auto-tuning command | U16 | R/W | 03·06·10 | 0 = Off / stop · 1 = Standard AT · 2 = Low-PV type AT printed p.38 (PDF p.41) | |
| 41006 | 1005 (0x03ED) | HR | P (proportional band) | U16 | ×0.1 % | R/W | 03·06·10 | Manual examples: 01 06 00 05 03 E8 99 75 (100.0 to 40006), 01 10 00 05 00 03 06 03 E8 00 64 00 32 56 BE (P, I, D at once). Same value as 40006 Range 0 ~ 999.9 % printed p.25~27 (PDF p.28~30), printed p.38 (PDF p.41) |
| 41007 | 1006 (0x03EE) | HR | I (integral time) | U16 | ×0.1 s | R/W | 03·06·10 | Range 0 ~ 3200 s printed p.38 (PDF p.41) |
| 41008 | 1007 (0x03EF) | HR | D (derivative time) | U16 | ×0.1 s | R/W | 03·06·10 | Range 0 ~ 999.9 s printed p.38 (PDF p.41) |
| 41016 | 1015 (0x03F7) | HR | Input type code | U16 | R/W | 03·06·10 | Range 0 ~ 16 printed p.38 (PDF p.41) | |
| 41017 | 1016 (0x03F8) | HR | Temperature unit | U16 | R/W | 03·06·10 | 0 = °C · 1 = °F printed p.38 (PDF p.41) | |
| 41018 | 1017 (0x03F9) | HR | Input scale lower limit (P-SL) | S16 | R/W | 03·06·10 | Range -1999 ~ 9999 printed p.38 (PDF p.41) | |
| 41019 | 1018 (0x03FA) | HR | Input scale upper limit (P-SU) | S16 | R/W | 03·06·10 | Range -1999 ~ 9999 printed p.38 (PDF p.41) | |
| 41020 | 1019 (0x03FB) | HR | Decimal point position (P-dP) | U16 | R/W | 03·06·10 | When changing the decimal point over communication, rewrite P-SL and P-SU too (e.g. 0-400 → 0.0-400.0: P-dP = 1, P-SL = 0, P-SU = 4000) Range 0 ~ 2 printed p.28 (PDF p.31) | |
| 41031 | 1030 (0x0406) | HR | SV lower limit (SV-L) | S16 | R/W | 03·06·10 | Manual example 02 03 04 06 00 02 25 09 → 0000h, 0190h (SV-L 0, SV-H 400) printed p.21 (PDF p.24), printed p.38 (PDF p.41) | |
| 41032 | 1031 (0x0407) | HR | SV upper limit (SV-H) | S16 | R/W | 03·06·10 | printed p.38 (PDF p.41) | |
| 41039 | 1038 (0x040E) | HR | Heater break alarm set value (HB) | U16 | ×0.1 A | R/W | 03·06·10 | Range 0 ~ 50 A printed p.39 (PDF p.42) |
| 41040 | 1039 (0x040F) | HR | Setting lock (LoC) | U16 | R/W | 03·06·10 | While locked, write requests get a normal reply but are not executed Range 0 ~ 5 printed p.25 (PDF p.28), printed p.39 (PDF p.42) | |
| 41041 | 1040 (0x0410) | HR | Alarm 1 type (ALM1) | U16 | R/W | 03·06·10 | Range 0 ~ 34 printed p.39 (PDF p.42) | |
| 41044 | 1043 (0x0413) | HR | Alarm 1 set value / lower limit (AL1, A1-L) | S16 | R/W | 03·06·10 | Engineering units (scaled to the input range), integer without decimal point; decimal places from 41020 (P-dP) printed p.39 (PDF p.42) | |
| 41045 | 1044 (0x0414) | HR | Alarm 2 set value / lower limit (AL2, A2-L) | S16 | R/W | 03·06·10 | printed p.39 (PDF p.42) | |
| 41082 | 1081 (0x0439) | HR | Ramp/soak command (ProG) | U16 | R/W | 03·06·10 | 0 = oFF stop · 1 = rUn start · 2 = HLd hold · 3 = End finished (read only) printed p.40 (PDF p.43) |
Notes
- Values that depend on the input range can be read from two tables: internal values (30001/40001-, 0.00-100.00 % of the input range) and engineering units (number + 1000, e.g. PV at 31001). This file lists mainly the engineering table. Range-independent values (PID etc.) read the same at both numbers (printed p.28).
- Parameters written over communication are saved to EEPROM automatically: 100,000-write limit, avoid cyclic writes (printed p.15). This manual (TN512642d) covers the earlier PXR (Micro Controller X). Page numbers are printed pages (PDF = printed + 3).
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- fuji-electric/pxr.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- Micro Controller X Communication Functions (RS-485 MODBUS) Type: PXR — Instruction Manual — Fuji Electric, INP-TN512642d-E · printed p.5 settings, pp.8-27 protocol and examples, pp.28-46 data format and address maps (PDF p.8, 11-30, 31-49) · checked 2026-10-29