Communication option of Micro Controller X (PXR3, 4, 5, 9). The same data comes in two tables: internal values (% of input range, 30001/40001-) and engineering units (+1000: 31001/41001-). PV, SV, DV, MV and alarm status (04); SV, PID, input range and alarm settings (03, 06, 10); FIX coil 00001 · Temperature controller · PXR3, PXR4, PXR5, PXR9

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)9600 bps — options: 9600
Data · parity · stop8 · Odd · 1
Max per request60 registers
Manual address style40001/30001 style (wire address + 1, first digit = table)

Registers (40)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

40

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
000010 (0x0000)COFIX (save settings to non-volatile memory)BITR/W01·05
1 = request. Manual example 01 05 00 00 FF 00 8C 3A. Saving takes about 5 s; do not power off meanwhile
printed p.24 (PDF p.27), printed p.31 (PDF p.34)
100010 (0x0000)DIAlarm 1 ON/OFFBITR02
printed p.37 (PDF p.40)
100054 (0x0004)DIAlarm 2 ON/OFFBITR02
printed p.37 (PDF p.40)
100098 (0x0008)DIAlarm 1 output (de-energizing alarm result)BITR02
printed p.37 (PDF p.40)
100109 (0x0009)DIAlarm 2 outputBITR02
printed p.37 (PDF p.40)
1001110 (0x000A)DIAlarm 3 outputBITR02
printed p.37 (PDF p.40)
1001211 (0x000B)DIHB (heater break) alarm relay outputBITR02
printed p.37 (PDF p.40)
1001312 (0x000C)DIAlarm 1 ON/OFF (same as 10001)BITR02
Manual example: 1F 02 00 0C 00 02 3A 76 → 01h (alarm 1 ON, alarm 2 OFF)
printed p.18 (PDF p.21), printed p.37 (PDF p.40)
1001413 (0x000D)DIAlarm 2 ON/OFFBITR02
printed p.37 (PDF p.40)
1001514 (0x000E)DIAlarm 3 ON/OFFBITR02
printed p.37 (PDF p.40)
300010 (0x0000)IRPV (internal value, %FS)S16×0.01 %R04
% of input range (0.00-100.00 %FS). Manual example 01 04 00 00 00 01 31 CA → 0346h = 8.38 %FS (33.5 °C on a 0-400 °C range)
printed p.22 (PDF p.25), printed p.36 (PDF p.39)
310011000 (0x03E8)IRPV (engineering units)S16R04
Manual example 01 04 03 E8 00 01 B1 BA → 014Fh = 335 (1 decimal → 33.5 °C). On input error, 105 % or −5 % of the range
printed p.23 (PDF p.26), printed p.42 (PDF p.45)
310021001 (0x03E9)IRSV in useS16R04
May differ from 40003/41003 (front-panel SV) during ramp/soak or SV switching; monitor this one
printed p.42 (PDF p.45)
310031002 (0x03EA)IRDeviation DV in useS16R04
Engineering units (scaled to the input range), integer without decimal point; decimal places from 41020 (P-dP)
printed p.42 (PDF p.45)
310041003 (0x03EB)IRMV (output 1)S16×0.01 %R04
Range -3 ~ 103 %
printed p.42 (PDF p.45)
310051004 (0x03EC)IRMV (output 2)S16×0.01 %R04
Range -3 ~ 103 %
printed p.42 (PDF p.45)
310061005 (0x03ED)IRStation numberU16R04
printed p.42 (PDF p.45)
310071006 (0x03EE)IRAlarm statusU16R04
b0 Alarm 1 output · b1 Alarm 2 output · b2 Alarm 3 output · b3 HB alarm relay output · b4 Alarm 1 ON · b5 Alarm 2 ON · b6 Alarm 3 ON · b7 HB alarm output
printed p.42 (PDF p.45), printed p.44 (PDF p.47)
310081007 (0x03EF)IRInput/main unit abnormal statusU16R04
b0 Input lower open circuit · b1 Input upper open circuit · b2 Input under-range · b3 Input over-range · b6 Setting range error · b7 EEPROM error
printed p.42 (PDF p.45), printed p.44 (PDF p.47)
310091008 (0x03F0)IRRamp/soak current positionU16R04
Range 0 ~ 17
printed p.42 (PDF p.45), printed p.45 (PDF p.48)
310101009 (0x03F1)IRHeater currentU16×0.1 AR04
Range 0 ~ 50 A
printed p.42 (PDF p.45)
410031002 (0x03EA)HRSV (front-panel set value)S16R/W03·06·10
Engineering units (scaled to the input range), integer without decimal point; decimal places from 41020 (P-dP)
printed p.38 (PDF p.41)
410041003 (0x03EB)HRControl RUN/standbyU16R/W03·06·10
0 = RUN (standby off) · 1 = Standby
printed p.38 (PDF p.41)
410051004 (0x03EC)HRAuto-tuning commandU16R/W03·06·10
0 = Off / stop · 1 = Standard AT · 2 = Low-PV type AT
printed p.38 (PDF p.41)
410061005 (0x03ED)HRP (proportional band)U16×0.1 %R/W03·06·10
Manual examples: 01 06 00 05 03 E8 99 75 (100.0 to 40006), 01 10 00 05 00 03 06 03 E8 00 64 00 32 56 BE (P, I, D at once). Same value as 40006
Range 0 ~ 999.9 %
printed p.25~27 (PDF p.28~30), printed p.38 (PDF p.41)
410071006 (0x03EE)HRI (integral time)U16×0.1 sR/W03·06·10
Range 0 ~ 3200 s
printed p.38 (PDF p.41)
410081007 (0x03EF)HRD (derivative time)U16×0.1 sR/W03·06·10
Range 0 ~ 999.9 s
printed p.38 (PDF p.41)
410161015 (0x03F7)HRInput type codeU16R/W03·06·10
Range 0 ~ 16
printed p.38 (PDF p.41)
410171016 (0x03F8)HRTemperature unitU16R/W03·06·10
0 = °C · 1 = °F
printed p.38 (PDF p.41)
410181017 (0x03F9)HRInput scale lower limit (P-SL)S16R/W03·06·10
Range -1999 ~ 9999
printed p.38 (PDF p.41)
410191018 (0x03FA)HRInput scale upper limit (P-SU)S16R/W03·06·10
Range -1999 ~ 9999
printed p.38 (PDF p.41)
410201019 (0x03FB)HRDecimal point position (P-dP)U16R/W03·06·10
When changing the decimal point over communication, rewrite P-SL and P-SU too (e.g. 0-400 → 0.0-400.0: P-dP = 1, P-SL = 0, P-SU = 4000)
Range 0 ~ 2
printed p.28 (PDF p.31)
410311030 (0x0406)HRSV lower limit (SV-L)S16R/W03·06·10
Manual example 02 03 04 06 00 02 25 09 → 0000h, 0190h (SV-L 0, SV-H 400)
printed p.21 (PDF p.24), printed p.38 (PDF p.41)
410321031 (0x0407)HRSV upper limit (SV-H)S16R/W03·06·10
printed p.38 (PDF p.41)
410391038 (0x040E)HRHeater break alarm set value (HB)U16×0.1 AR/W03·06·10
Range 0 ~ 50 A
printed p.39 (PDF p.42)
410401039 (0x040F)HRSetting lock (LoC)U16R/W03·06·10
While locked, write requests get a normal reply but are not executed
Range 0 ~ 5
printed p.25 (PDF p.28), printed p.39 (PDF p.42)
410411040 (0x0410)HRAlarm 1 type (ALM1)U16R/W03·06·10
Range 0 ~ 34
printed p.39 (PDF p.42)
410441043 (0x0413)HRAlarm 1 set value / lower limit (AL1, A1-L)S16R/W03·06·10
Engineering units (scaled to the input range), integer without decimal point; decimal places from 41020 (P-dP)
printed p.39 (PDF p.42)
410451044 (0x0414)HRAlarm 2 set value / lower limit (AL2, A2-L)S16R/W03·06·10
printed p.39 (PDF p.42)
410821081 (0x0439)HRRamp/soak command (ProG)U16R/W03·06·10
0 = oFF stop · 1 = rUn start · 2 = HLd hold · 3 = End finished (read only)
printed p.40 (PDF p.43)

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).