An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 38400 bps — options: 4800, 9600, 19200, 38400 |
| Data · parity · stop | 8 · Even · 1 |
| Slave ID (factory) | 1 (1~99) |
| Manual address style | Wire address as is (0-based) |
- The communication manual writes «300001 (0000)»: 1-based reference number plus hex communication address in parentheses. Each table starts at (0000), so the parenthesized value is used as the 0-based wire address (comm manual pp.25-36).
- Communication spec (product manual p.3): 4800/9600/19200/38400 (default) bps; 8 data bits, even parity, 1 stop bit fixed. Address Addr default 1 (1-99); communication write ComW default EnA (product manual p.6).
Registers (30)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 300001 (0000) | 0 (0x0000) | IR | U-V line load voltage | U16 | ×0.1 V | R | 04 | p.25 |
| 300002 (0001) | 1 (0x0001) | IR | V-W line load voltage | U16 | ×0.1 V | R | 04 | p.25 |
| 300003 (0002) | 2 (0x0002) | IR | W-U line load voltage | U16 | ×0.1 V | R | 04 | p.25 |
| 300004 (0003) | 3 (0x0003) | IR | U-phase load current | U16 | ×0.1 A | R | 04 | p.25 |
| 300005 (0004) | 4 (0x0004) | IR | V-phase load current | U16 | ×0.1 A | R | 04 | p.25 |
| 300006 (0005) | 5 (0x0005) | IR | W-phase load current | U16 | ×0.1 A | R | 04 | p.25 |
| 300007 (0006) | 6 (0x0006) | IR | Power | U16 | ×0.01 W | R | 04 | p.25 |
| 300008 (0007) | 7 (0x0007) | IR | Load status | U16 | ×0.1 % | R | 04 | p.25 |
| 300009 (0008) | 8 (0x0008) | IR | Power frequency | U16 | ×0.01 Hz | R | 04 | p.25 |
| 400001 (0000) | 0 (0x0000) | HR | Reference value (communication control input) | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 100 % p.32 |
| 400002 (0001) | 1 (0x0001) | HR | Start limit time | U16 | s | R/W | 03·06·10 | Range 0 ~ 100 s p.32 |
| 400003 (0002) | 2 (0x0002) | HR | Start limit | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 110 % p.32 |
| 400004 (0003) | 3 (0x0003) | HR | Soft start time | U16 | s | R/W | 03·06·10 | Range 0 ~ 100 s p.32 |
| 400005 (0004) | 4 (0x0004) | HR | Output high-limit value | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 110 % p.32 |
| 400006 (0005) | 5 (0x0005) | HR | Output low-limit value | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 110 % p.32 |
| 400007 (0006) | 6 (0x0006) | HR | Remote SP1 | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 100 % p.32 |
| 400013 (000C) | 12 (0x000C) | HR | Soft up time | U16 | s | R/W | 03·06·10 | Range 0 ~ 999 s p.32 |
| 400014 (000D) | 13 (0x000D) | HR | Soft down time | U16 | s | R/W | 03·06·10 | Range 0 ~ 999 s p.32 |
| 400015 (000E) | 14 (0x000E) | HR | Current limit | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 110 % p.32 |
| 400016 (000F) | 15 (0x000F) | HR | Overcurrent alarm value | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 120 % p.32 |
| 400017 (0010) | 16 (0x0010) | HR | Overcurrent delay time | U16 | s | R/W | 03·06·10 | Range 0 ~ 100 s p.32 |
| 400018 (0011) | 17 (0x0011) | HR | Overvoltage alarm value | U16 | ×0.1 % | R/W | 03·06·10 | Range 0 ~ 300 % p.33 |
| 400020 (0013) | 19 (0x0013) | HR | Heater break alarm value | U16 | ×0.1 % | R/W | 03·06·10 | Range 10 ~ 500 % p.33 |
| 400021 (0014) | 20 (0x0014) | HR | Display value content | U16 | R/W | 03·06·10 | 0 = U-V line load voltage (default) · 1 = V-W line load voltage · 2 = W-U line load voltage · 3 = U-phase load current · 4 = V-phase load current · 5 = W-phase load current · 6 = Load power · 7 = Control input p.33 | |
| 400023 (0016) | 22 (0x0016) | HR | Proportional constant | U16 | R/W | 03·06·10 | Range 1 ~ 2000 p.33 | |
| 400024 (0017) | 23 (0x0017) | HR | Integral constant | U16 | ×0.1 s | R/W | 03·06·10 | Range 0.1 ~ 999.9 s p.33 |
| 400025 (0018) | 24 (0x0018) | HR | Control method | U16 | R/W | 03·06·10 | 1 = Fixed cycle control · 2 = ON/OFF control · 3 = Phase control (default) · 4 = Constant voltage feedback · 5 = Constant current feedback · 6 = Constant power feedback p.33 | |
| 400026 (0019) | 25 (0x0019) | HR | Digital input 1 | U16 | R/W | 03·06·10 | 0 = Multi setting point · 1 = Single setting point 1 · 2 = Single setting point 2 · 3 = Single setting point 3 · 4 = Reset · 5 = HOLD p.34 | |
| 400029 (001C) | 28 (0x001C) | HR | Control input type | U16 | R/W | 03·06·10 | 0 = 4-20 mA (default) · 1 = 0-20 mA · 2 = 1-5 VDC · 3 = 0-5 VDC · 4 = 0-10 VDC · 5 = SSR contact · 6 = RS485 communication p.34 | |
| 400031 (001E) | 30 (0x001E) | HR | Operation status | U16 | R | 03 | Not saved (Save N) b0 At least one of bits 1-9 · b1 Over 150 % overcurrent · b2 Over 110 % overcurrent · b3 Overvoltage · b4 Temperature error · b5 Fuse break · b6 3-phase voltage phase difference unbalance · b7 No load · b8 SCR error · b9 Frequency error · b12 1 run, 0 stop · b13 1 manual, 0 auto · b14 1 digital input p.35 |
Notes
- Weights, units and save flags are as in the comm manual tables (×0.1 → scale 0.1). Parameters not settable on the device can still be changed via communication (p.36). DPU1 (single-phase) has a different input register layout and has its own file (autonics/dpu1). On DPU3 the power weight is ×0.01, the overvoltage alarm range is 0-300 %, and there is no variable cycle control method (as in the tables).
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- autonics/dpu3.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.