An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).
Default communication
| Protocol | Modbus RTU |
|---|---|
| Baud (factory) | 9600 bps — options: 2400, 4800, 9600, 19200, 38400 |
| Data · parity · stop | 8 · None · 2 |
| Slave ID (factory) | 1 (1~127) |
| 32-bit order | CDAB |
| Manual address style | Wire address as is (0-based) |
- Comm spec/defaults from product manual TCD220014AC: 9600 bps, 8 data bits fixed, parity none, 2 stop bits, response wait 20 ms, address 001 (1-127), up to 31 units.
- Manual writes «400001 (0000)»: 1-based reference plus hex comm address; first entries are (0000), so the parenthesized value is the 0-based wire address (pp.21-27). Frame examples show layout only.
- 2-word values put the low word at the lower address (e.g. 301004 low, 301005 high), i.e. CDAB (p.24).
- Broadcast is not supported (comm manual p.v).
Registers (39)
«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.
Swipe the table sideways — the first column (manual address) stays put.
| Manual | Wire | Table | Name | Type | Unit · scale | R/W | FC | Details |
|---|---|---|---|---|---|---|---|---|
| 000001 (0000) | 0 (0x0000) | CO | Reset | BIT | R/W | 01·05 | Write ON (FF00h) with FC05 to reset. 0 = OFF · 1 = ON p.21 2.1 | |
| 000002 (0001) | 1 (0x0001) | CO | OUT2 output | BIT | R | 01 | 0 = OFF · 1 = ON p.21 2.1 | |
| 000003 (0002) | 2 (0x0002) | CO | OUT1 output | BIT | R | 01 | 0 = OFF · 1 = ON p.21 2.1 | |
| 000004 (0003) | 3 (0x0003) | CO | BATCH output | BIT | R | 01 | BATCH output models 0 = OFF · 1 = ON p.21 2.1 | |
| 000005 (0004) | 4 (0x0004) | CO | BATCH reset | BIT | R/W | 01·05 | BATCH output models; write ON (FF00h) with FC05 to reset. 0 = OFF · 1 = ON p.21 2.1 | |
| 100001 (0000) | 0 (0x0000) | DI | INA input status | BIT | R | 02 | 0 = OFF · 1 = ON p.21 2.2 | |
| 100002 (0001) | 1 (0x0001) | DI | INB input status | BIT | R | 02 | 0 = OFF · 1 = ON p.21 2.2 | |
| 100003 (0002) | 2 (0x0002) | DI | INHIBIT input status | BIT | R | 02 | 0 = OFF · 1 = ON p.21 2.2 | |
| 100004 (0003) | 3 (0x0003) | DI | RESET input status | BIT | R | 02 | 0 = OFF · 1 = ON p.21 2.2 | |
| 100005 (0004) | 4 (0x0004) | DI | BATCH RESET input status | BIT | R | 02 | 0 = OFF · 1 = ON p.21 2.2 | |
| 301001 (03E8) | 1000 (0x03E8) | IR | LED display status bits | U16 | R | 04 | Bit layout per the table on p.24. b5 BA.O · b6 OUT2 · b7 OUT1 · b10 BA.S · b11 LOCK · b12 PRESET2 · b13 PRESET1 · b14 TMR · b15 CNT p.23 2.4 | |
| 301002 (03E9) | 1001 (0x03E9) | IR | BATCH counter present value | U32 CDAB | R | 04 | BATCH output models. 2-word value; lower address holds the low word (p.24). Range 0 ~ 999999 p.23 2.4 | |
| 301004 (03EB) | 1003 (0x03EB) | IR | Counter/timer present value | S32 CDAB | R | 04 | Counter: 6-digit -99999..999999, 4-digit -999..9999 / timer: within time range. 2-word value; lower address holds the low word (p.24). p.23 2.4 | |
| 301006 (03ED) | 1005 (0x03ED) | IR | Display unit | U16 | R | 04 | Counter: decimal point of display value (400058); timer: time range (400102). p.23 2.4 | |
| 301007 (03EE) | 1006 (0x03EE) | IR | PRESET2 setting value | S32 CDAB | R | 04 | Counter: 6-digit -99999..999999, 4-digit -999..9999 / timer: within time range. 2-word value; lower address holds the low word (p.24). p.23 2.4 | |
| 301009 (03F0) | 1008 (0x03F0) | IR | PRESET1 setting value | S32 CDAB | R | 04 | Counter: 6-digit -99999..999999, 4-digit -999..9999 / timer: within time range. 2-word value; lower address holds the low word (p.24). p.23 2.4 | |
| 301011 (03F2) | 1010 (0x03F2) | IR | BATCH counter setting value | U32 CDAB | R | 04 | 2-word value; lower address holds the low word (p.24). Range 0 ~ 999999 p.23 2.4 | |
| 301013 (03F4) | 1012 (0x03F4) | IR | Input logic | U16 | R | 04 | 0 = NPN · 1 = PNP p.23 2.4 | |
| 400001 (0000) | 0 (0x0000) | HR | PRESET2 setting value | U32 CDAB | R/W | 03·10 | Counter: 6-digit 0..999999, 4-digit 0..9999 / timer: within time range. 2-word value; lower address holds the low word (p.24). p.24 2.5 | |
| 400003 (0002) | 2 (0x0002) | HR | PRESET1 setting value | U32 CDAB | R/W | 03·10 | Counter: 6-digit 0..999999, 4-digit 0..9999 / timer: within time range. 2-word value; lower address holds the low word (p.24). p.24 2.5 | |
| 400005 (0004) | 4 (0x0004) | HR | BATCH counter setting value | U32 CDAB | R/W | 03·10 | 2-word value; lower address holds the low word (p.24). Range 0 ~ 999999 p.24 2.5 | |
| 400051 (0032) | 50 (0x0032) | HR | Counter/Timer [C-T] | U16 | R/W | 03·06·10 | 0 = Counter (COUN) · 1 = Timer (TIME) p.25 2.6.1 | |
| 400052 (0033) | 51 (0x0033) | HR | Input mode [IN] | U16 | R/W | 03·06·10 | 0 = UP · 1 = UP-1 · 2 = UP-2 · 3 = DN · 4 = DN-1 · 5 = DN-2 · 6 = UD-A · 7 = UD-B · 8 = UD-C p.25 2.6.1 | |
| 400053 (0034) | 52 (0x0034) | HR | Indication mode (indicator) | U16 | R/W | 03·06·10 | 0 = TOTAL · 1 = HOLD p.25 2.6.1 | |
| 400054 (0035) | 53 (0x0035) | HR | Output mode [OUTM] | U16 | R/W | 03·06·10 | 0 = F · 1 = N · 2 = C · 3 = R · 4 = K · 5 = P · 6 = Q · 7 = A · 8 = S · 9 = T · 10 = D p.25 2.6.1 | |
| 400055 (0036) | 54 (0x0036) | HR | Max. counting speed [CPS] | U16 | R/W | 03·06·10 | 0 = 1 cps · 1 = 30 cps · 2 = 1k cps · 3 = 5k cps · 4 = 10k cps p.25 2.6.1 | |
| 400056 (0037) | 55 (0x0037) | HR | OUT2 output time | U16 | ×0.01 s | R/W | 03·06·10 | Unit ×10 ms (0.01-99.99 s) Range 0.01 ~ 99.99 s p.25 2.6.1 |
| 400057 (0038) | 56 (0x0038) | HR | OUT1 output time | U16 | ×0.01 s | R/W | 03·06·10 | Unit ×10 ms (0.01-99.99 s) Range 0.01 ~ 99.99 s p.25 2.6.1 |
| 400058 (0039) | 57 (0x0039) | HR | Decimal point [DP] | U16 | R/W | 03·06·10 | 6-digit notation; 4-digit: 0 ----, 1 ---.-, 2 --.--, 3 -.--- 0 = ------ · 1 = -----.- · 2 = ----.-- · 3 = ---.--- · 4 = --.---- · 5 = -.----- p.25 2.6.1 | |
| 400059 (003A) | 58 (0x003A) | HR | Min. reset time [RST] | U16 | R/W | 03·06·10 | 0 = 1 ms · 1 = 20 ms p.25 2.6.1 | |
| 400065 (0040) | 64 (0x0040) | HR | Memory protection [DATA] | U16 | R/W | 03·06·10 | 0 = CLR · 1 = REC p.25 2.6.1 | |
| 400066 (0041) | 65 (0x0041) | HR | Lock key [LOCK] | U16 | R/W | 03·06·10 | 0 = LOFF · 1 = LOC1 · 2 = LOC2 · 3 = LOC3 p.25 2.6.1 | |
| 400101 (0064) | 100 (0x0064) | HR | Counter/Timer [C-T] (timer group) | U16 | R/W | 03·06·10 | 0 = Counter (COUN) · 1 = Timer (TIME) p.26 2.6.2 | |
| 400151 (0096) | 150 (0x0096) | HR | Comm. address [ADDR] | U16 | R/W | 03·06·10 | Range 1 ~ 127 p.27 2.6.3 | |
| 400152 (0097) | 151 (0x0097) | HR | Comm. speed [BPS] | U16 | R/W | 03·06·10 | 0 = 2400 bps · 1 = 4800 bps · 2 = 9600 bps · 3 = 19200 bps · 4 = 38400 bps p.27 2.6.3 | |
| 400153 (0098) | 152 (0x0098) | HR | Comm. parity bit [PRTY] | U16 | R/W | 03·06·10 | 0 = NONE · 1 = EVEN · 2 = ODD p.27 2.6.3 | |
| 400154 (0099) | 153 (0x0099) | HR | Comm. stop bit [STP] | U16 | R/W | 03·06·10 | 0 = 1 bit · 1 = 2 bits p.27 2.6.3 | |
| 400155 (009A) | 154 (0x009A) | HR | Response waiting time [RSWT] | U16 | ms | R/W | 03·06·10 | Range 5 ~ 99 ms p.27 2.6.3 |
| 400156 (009B) | 155 (0x009B) | HR | Comm. writing [COMW] | U16 | R/W | 03·06·10 | 0 = ENA · 1 = DISA p.27 2.6.3 |
Notes
- RS485 only on models with communication code T (ordering: CT ① digits ② size - ③ output ④ power ⑤ T). In models, □ = size (S/Y/M), output (1P/2P/I), power (2/4); not all combinations exist.
- Changing counter/timer group values via FC06/16 flashes COMW/RST for 3 s and resets the present value; preset/comm group changes keep it (p.27).
- The 2-word presets (400001-400006) list 03/06/16, but 06 writes one word only, so only 03/16 are listed here.
- FC06 is recommended over FC16 for PLCs/graphic panels (p.18).
- Timer group (400101-400110) time range/output mode codes depend on 4/6-digit type; only C-T is included (p.26).
Read it with PortDock
- Install the free PortDock Modbus Master and connect with the device's settings.
- On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
- Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
- To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.
To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).
Download JSON
- autonics/ct.json (GitHub raw) · copy on this site · history
- schema.json — format (JSON Schema). table, address (0-based), type and order match the PortDock CSV.
- License: CC BY 4.0 — please cite:
PortDock device register maps, v2026.11 · 51509f0445a9, https://portdock.dev/devices/
and this page. LICENSE · data bundle, version and changelog - Found a mistake? Please open a GitHub issue with the manual page.
Sources
- User Manual for Communication Counters/Timers CT Series MCC-CTC1-V1.3-EN — Autonics, MCC-CTC1-V1.3-EN (2025-08-05) · pp.21-27 mapping table (printed page = PDF page) · checked 2026-10-22
- Counters / Timers CT Series PRODUCT MANUAL TCD220014AC — Autonics, CT_EN_TCD220014AC_20240228 · p.2 ordering information, 'Communication Interface' spec, communication parameter table · checked 2026-10-22