Autonics DPU1 Series Modbus register map

SCR power controller. Input registers (output voltage, load current, power, frequency); holding registers (communication control input, start/limits, alarms, control method; FC 03/06/16). · Other

An unofficial summary of facts (addresses, types, units, scaling) from the maker's manual. Not affiliated with the maker; values can differ by firmware or model. Always check the device manual before writing (run commands, settings).

Default communication

ProtocolModbus RTU
Baud (factory)38400 bps — options: 4800, 9600, 19200, 38400
Data · parity · stop8 · Even · 1
Slave ID (factory)1 (1~99)
Manual address styleWire address as is (0-based)

Registers (26)

«Wire» is the 0-based address in the request frame (PortDock's «0-based» notation). Value = raw × scale. Table: HR holding register, IR input register, CO coil, DI discrete input. Function codes in hex.

26

Swipe the table sideways — the first column (manual address) stays put.

ManualWireTableNameTypeUnit · scaleR/WFCDetails
300001 (0000)0 (0x0000)IROutput voltageU16×0.1 VR04
p.23
300002 (0001)1 (0x0001)IRLoad currentU16×0.1 AR04
p.23
300003 (0002)2 (0x0002)IRPowerU16×0.1 WR04
p.23
300004 (0003)3 (0x0003)IRLoad statusU16×0.1 %R04
p.23
300005 (0004)4 (0x0004)IRPower frequencyU16×0.01 HzR04
p.23
400001 (0000)0 (0x0000)HRReference value (communication control input)U16×0.1 %R/W03·06·10
Range 0 ~ 100 %
p.27
400002 (0001)1 (0x0001)HRStart limit timeU16sR/W03·06·10
Range 0 ~ 100 s
p.27
400003 (0002)2 (0x0002)HRStart limitU16×0.1 %R/W03·06·10
Range 0 ~ 110 %
p.27
400004 (0003)3 (0x0003)HRSoft start timeU16sR/W03·06·10
Range 0 ~ 100 s
p.27
400005 (0004)4 (0x0004)HROutput high-limit valueU16×0.1 %R/W03·06·10
Range 0 ~ 110 %
p.27
400006 (0005)5 (0x0005)HROutput low-limit valueU16×0.1 %R/W03·06·10
Range 0 ~ 110 %
p.27
400007 (0006)6 (0x0006)HRRemote SP1U16×0.1 %R/W03·06·10
Range 0 ~ 100 %
p.27
400013 (000C)12 (0x000C)HRSoft up timeU16sR/W03·06·10
Range 0 ~ 999 s
p.27
400014 (000D)13 (0x000D)HRSoft down timeU16sR/W03·06·10
Range 0 ~ 999 s
p.27
400015 (000E)14 (0x000E)HRCurrent limitU16×0.1 %R/W03·06·10
Range 0 ~ 110 %
p.27
400016 (000F)15 (0x000F)HROvercurrent alarm valueU16×0.1 %R/W03·06·10
Range 0 ~ 120 %
p.28
400017 (0010)16 (0x0010)HROvercurrent delay timeU16sR/W03·06·10
Range 0 ~ 100 s
p.28
400018 (0011)17 (0x0011)HROvervoltage alarm valueU16×0.1 %R/W03·06·10
Range 0 ~ 120 %
p.28
400020 (0013)19 (0x0013)HRHeater break alarm valueU16×0.1 %R/W03·06·10
Range 10 ~ 500 %
p.28
400021 (0014)20 (0x0014)HRDisplay value contentU16R/W03·06·10
0 = Load voltage (default) · 1 = Load current · 2 = Load power · 3 = Control input
p.28
400023 (0016)22 (0x0016)HRProportional constantU16R/W03·06·10
Range 1 ~ 2000
p.28
400024 (0017)23 (0x0017)HRIntegral constantU16×0.1 sR/W03·06·10
Range 0.1 ~ 999.9 s
p.28
400025 (0018)24 (0x0018)HRControl methodU16R/W03·06·10
0 = Fixed cycle control · 1 = Variable cycle control · 2 = ON/OFF control · 3 = Phase control (default) · 4 = Constant voltage feedback · 5 = Constant current feedback · 6 = Constant power feedback
p.28
400026 (0019)25 (0x0019)HRDigital input 1U16R/W03·06·10
0 = Multi setting point · 1 = Single setting point 1 · 2 = Single setting point 2 · 3 = Single setting point 3 · 4 = Reset · 5 = HOLD
p.29
400029 (001C)28 (0x001C)HRControl input typeU16R/W03·06·10
0 = 4-20 mA (default) · 1 = 0-20 mA · 2 = 1-5 VDC · 3 = 0-5 VDC · 4 = 0-10 VDC · 5 = SSR contact · 6 = RS485 communication
p.29
400031 (001E)30 (0x001E)HROperation statusU16R03
Not saved (Save N)
b0 At least one of bits 1-9 · b1 Over 150 % overcurrent · b2 Over 110 % overcurrent · b3 Overvoltage · b4 Temperature error · b5 Fuse break · b7 No load · b8 SCR error · b9 Frequency error · b12 1 run, 0 stop · b13 1 manual, 0 auto · b14 1 digital input
p.30

Notes

Read it with PortDock

  1. Install the free PortDock Modbus Master and connect with the device's settings.
  2. On the table toolbar, «Device profile…» → pick this device → «Load». Polling tables, names, types and the Slave ID are filled in (optionally the serial settings too).
  3. Names carry the unit and scale (e.g. «×0.01 Hz»). Values on screen are raw — multiply by the scale.
  4. To test your program without the device, PortDock Modbus Slave's «Emulate device…» serves the same map with example values.

To draw the RS-485 wiring, open the wiring diagram maker pre-filled with this device's name, slave ID, baud rate and parity (check terminal numbers in the manual).